| Plan Review Notes For Permit 17121004 |
| Permit Number |
17121004 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-04-17 14:53:34 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | 4. OK | | | 5. OK | | | 6. OK | | | 7. OK | | | 8. ADDRESS ON PERMIT APPLICATION IS 445 LILAC CT., PLAN | | | SHOWS AN ADDRESS ON 451 LILAC CT. PLAN ALSO STATES THIS | | | IS A LEVEL 2 ALTERATION, BUT APPLICATION STATES THIS IS | | | A NEW HOUSE. PROVIDE CORRECTIONS. FBC 107.2.1 | | | 9. | | | 10.OK | | | 11. FEED TO INTERIOR PANEL FROM DISCONNECT IS REQUIRED | | | TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR, SIZED PER | | | CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE E3704.6, | | | 3607.3.1 | | | 12. PROVIDE LOCATION OF DISCONNECT ON PLAN. FBC 107.2.1 | | | | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | PHIL PETTY | | | ELECTRICAL PLANS EXAMINER , CHIEF ELECTRICAL INSPECTOR | | | 561-805-6742 | | | [email protected] | | | |
|