| Date |
Text |
| 2018-04-25 10:57:54 | |
| | |
| | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | 561-805-6718 [email protected] |
| | |
| | |
| | NEW SINGLE FAMILY RESIDENCE (R3), BUILDING REVIEW |
| | COMMENTS. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | SECOND REVIEW: |
| | |
| | 5- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. |
| | R401.3 FBC-RESIDENTIAL. |
| | |
| | NOT ADDRESSED. NOTE: NEED DRAINAGE PLAN. SEE CITY |
| | AMENDMENTS SEC. 107.2.5 BELOW. |
| | |
| | PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC. |
| | R401.3 FBC-RESIDENTIAL. |
| | |
| | |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| | DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN |
| | SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE |
| | SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE |
| | FIRST 10 FEET (3048 MM). |
| | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| | CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| | IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| | BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| | PERCENT AWAY FROM THE BUILDING. |
| | |
| | |
| | |
| | ------------------------------------------------------- |
| | ----------------------------- |
| | |
| | DEFERRED SUBMITTALS |
| | |
| | 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.001 FOR: |
| | |
| | A) ENTRY DOOR WITH SIDELITES AND TRANSOM AS SHOWN ON |
| | PLANS. |
| | |
| | B) SINGLE HUNG WINDOWS AS SPECIFIED ON PLANS. |
| | |
| | C) HORIZONTAL ROLLER WINDOWS AS SPECIFIED ON PLANS. |
| | |
| | D) SLIDING GLASS DOORS AS SHOWN ON PLANS. |
| | |
| | E) HURRICANE SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| | HURRICANE IMPACT GLAZING. AND, PROVIDE COMPLETE |
| | INSTALLATION SCHEDULE. SEE CITY SAMPLE. |
| | |
| | F) ROOF SHINGLES. |
| | |
| | G) ROOF SHINGLES UNDERLAYMENT AS SPECIFIED ON PLANS. |
| | (COORDINATE WITH ITEM #9(B) ABOVE. |
| | |
| | H) RIDGE VENTS AS SPECIFIED ON PLANS. SEE SHEET A-1. |
| | |
| | I) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| | |
| | 13- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL |
| | PRODUCT APPROVALS (NOT SIGNING AND SEALING) AS REQUIRED |
| | BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | |