| 2018-01-19 10:15:58 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. BREAKER FOR WATER HEATER IS STATED AS 30 AMP, WHICH |
| | IS TOO LARGE FOR THIS LOAD. BREAKER SHOULD BE SIZED AT |
| | 125% OF THE LOAD, WHICH IS A 25 AMP. PROVIDE |
| | CORRECTION. NEC 422.13; FBC RE3702.10 |
| | 2. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE3609.3 |
| | 3. PROVIDE GFCI PROTECTION FOR ALL OUTLETS IN GARAGE, |
| | INCLUDING THE GARAGE DOOR OPENER. NEC 210.8; FBC |
| | RE3902.2 |
| | 4. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| | TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| | ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| | NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| | INSTALLED AT THE FRONT AND BACK OF THE DWELLING. BACK |
| | OF HOUSE RECEPTACLE IS MISSING, FRONT OF HOUSE IS NOT |
| | SHOWN AS GFCI PROTECTED. PROVIDE CORRECTION. NEC 210.8, |
| | 210.52(E)(1) FBC RE E3901.7, E3902.3 |
| | 5. A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH |
| | CIRCUITS SHALL HAVE NO OTHER OUTLETS. PROVIDE |
| | CORRECTION. NEC 210.11(C)(3) , FBC RE3703.4 |
| | 6. ALL RECEPTACLES IN KITCHEN REQUIRE GFCI PROTECTION. |
| | ALSO, THE WALL SPACING OF OUTLETS IS NOT PER CODE. |
| | PROVIDE CORRECTIONS. NEC 210.8, 210.52(C)(1); FBC |
| | RE3901.4, E3902.6 |
| | 7. A GFCI PROTECTED OUTLET ON A 20 AMP CIRCUIT IS |
| | REQUIRED WITHIN 3 FEET OF EACH BASIN. PROVIDE |
| | CORRECTION FOR MASTER BATH. NEC 210.11(C)(3), |
| | 210.52(D); FBC RE 3703.4, 3901.6 |
| | 8. ADDRESS ON PERMIT APPLICATION IS 445 LILAC CT., PLAN |
| | SHOWS AN ADDRESS ON 451 LILAC CT. PLAN ALSO STATES THIS |
| | IS A LEVEL 2 ALTERATION, BUT APPLICATION STATES THIS IS |
| | A NEW HOUSE. PROVIDE CORRECTIONS. FBC 107.2.1 |
| | 9. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| | LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| | THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| | CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| | FBC EC R404.1 |
| | 10. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE4002.14 |
| | 11. FEED TO INTERIOR PANEL FROM DISCONNECT IS REQUIRED |
| | TO HAVE AN EQUIPMENT GROUNDING CONDUCTOR, SIZED PER |
| | CODE. PROVIDE CORRECTION. NEC 250.122; FBC RE E3704.6, |
| | 3607.3.1 |
| | 12. PROVIDE LOCATION OF METER AND DISCONNECT ON PLAN. |
| | FBC 107.2.1 |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |