| 2018-08-28 15:40:15 | PERMIT 17 120974 |
| | GAS REVIEW SEQUENCE 2 |
| | |
| | COMMENTS FROM SEQUENCE 1 |
| | |
| | 1. SIZE THE BRANCH TO GENERATOR. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | RESPONSE: REFER TO REVISED GAS PIPING ISOMETRIC ON |
| | SHEET P201 |
| | SEQUENCE 2 COMMENT(S): APPROVED |
| | |
| | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR INDOOR |
| | APPLIANCES PER THE FBC-2014 FUEL GAS CODE SEC. 304. |
| | RESPONSE: ALL APPLIANCES ARE OUTDOORS EXCEPT KITCHEN |
| | RANGE |
| | SEQUENCE 2 COMMENT(S): SUBMIT CALCULATIONS FOR |
| | COMBUSTION AIR FOR KITCHEN RANGE (SEE FBC RES G2407) |
| | CONFIRM MECHANICAL IS USING THOSE CALCULATION WHEN |
| | PROVIDING OUTSIDE AIR. |
| | |
| | 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS AND |
| | INSTALLATION GUIDES FOR ALL GAS EQUIPMENT AND |
| | REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 |
| | RESPONSE: REFER TO ATTACHED SPECIFICATION SHEETS |
| | SEQUENCE 2 COMMENT(S): ONLY RECEIVED SPECIFICATION |
| | SHEETS FOR OUTSIDE GRILL. SUBMIT SPECIFICATION SHEETS |
| | FOR GAS GENERATOR, KITCHEN GAS RANGE, FIREPLACES (SEE |
| | NOTES ON A406.1 AND A406.2), GWH 1 AND GWH 2, |
| | |
| | 4. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE |
| | SEC. 502 THRU 505. |
| | RESPONSE: REFER TO REVISED SHEETS P201 AND P101 FOR U/G |
| | PIPE GAS VENT |
| | SEQUENCE 2 COMMENT(S): APPROVED |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |