| 2018-01-11 10:30:48 | 1ST REVIEW FBC-2014 BUILDING |
| | PERMIT #17120971 |
| | 1/11/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ENGINEERING FOR INSTALLATION OF THE RTU IS |
| | INCOMPLETE: |
| | |
| | A) PROVIDE STRUCTURAL DETAILS FOR THE NEW ROOF OPENING. |
| | |
| | B) PROVIDE THE WIND LOAD DESIGN CRITERIA AS OUTLINED IN |
| | SECTION 1609 FBC-14 BUILDING. |
| | |
| | C) PROVIDE THE NOA FOR THE THYBAR CURB WITH SHOP |
| | DRAWING STAMP BY THE EOR. |
| | |
| | D) PROVIDE COMPLETE ATTACHMENT DETAILS- CURB TO ROOF, |
| | RTU TO CURB. |
| | |
| | 2) CLARIFY HOW ACCESS TO THE NEW RTU WILL BE PROVIDED. |
| | WHAT IS THE HEIGHT OF THE ROOF SURFACE FROM GRADE- SEE |
| | SECTION 306.5. |
| | |
| | 3) PLEASE CLARIFY WHY AIR CONDITIONING IS BEING |
| | PROVIDED FOR A WAREHOUSE. IDENTIFY WHAT PURPOSE THE |
| | SPACE WILL SEVE AND WHAT MATERIALS WILL BE STORED |
| | THERE. |
| | |
| | 4) ENERGYGAUGE COMPLIANCE FORM AND INPUT DATA REPORT: |
| | |
| | A) NO DATA PROVIDED FOR THE OVERHEAD DOORS. |
| | |
| | B) NO DATA PROVIDED FOR THE NORTH AND WEST WALLS |
| | ENCLOSING THE 3100 SF WAREHOUSE BUILDING. |
| | |
| | C) SHOW ON THE PLANS WHERE ALL THE INSULATIONS THAT ARE |
| | LISTED ON PAGE 5 OF THE INPUT DATA REPORT ARE TO BE |
| | INSTALLED OR ARE EXISTING. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |