2018-01-11 10:30:481ST REVIEW FBC-2014 BUILDING
 PERMIT #17120971
 1/11/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ENGINEERING FOR INSTALLATION OF THE RTU IS
 INCOMPLETE:
  
 A) PROVIDE STRUCTURAL DETAILS FOR THE NEW ROOF OPENING.
  
 B) PROVIDE THE WIND LOAD DESIGN CRITERIA AS OUTLINED IN
 SECTION 1609 FBC-14 BUILDING.
  
 C) PROVIDE THE NOA FOR THE THYBAR CURB WITH SHOP
 DRAWING STAMP BY THE EOR.
  
 D) PROVIDE COMPLETE ATTACHMENT DETAILS- CURB TO ROOF,
 RTU TO CURB.
  
 2) CLARIFY HOW ACCESS TO THE NEW RTU WILL BE PROVIDED.
 WHAT IS THE HEIGHT OF THE ROOF SURFACE FROM GRADE- SEE
 SECTION 306.5.
  
 3) PLEASE CLARIFY WHY AIR CONDITIONING IS BEING
 PROVIDED FOR A WAREHOUSE. IDENTIFY WHAT PURPOSE THE
 SPACE WILL SEVE AND WHAT MATERIALS WILL BE STORED
 THERE.
  
 4) ENERGYGAUGE COMPLIANCE FORM AND INPUT DATA REPORT:
  
 A) NO DATA PROVIDED FOR THE OVERHEAD DOORS.
  
 B) NO DATA PROVIDED FOR THE NORTH AND WEST WALLS
 ENCLOSING THE 3100 SF WAREHOUSE BUILDING.
  
 C) SHOW ON THE PLANS WHERE ALL THE INSULATIONS THAT ARE
 LISTED ON PAGE 5 OF THE INPUT DATA REPORT ARE TO BE
 INSTALLED OR ARE EXISTING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  