| Plan Review Notes For Permit 17120971 |
| Permit Number |
17120971 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-11 11:33:53 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. A DISCREPANCY EXIST BETWEEN PANEL SCHEDULE AND | | | ELECTRICAL PLAN IN REFERENCE TO THE FUSE SIZE OF | | | DISCONNECT. THE PLAN STATES THAT THE FUSE IS 125 AMP | | | AND THE PANEL SCHEDULE STATES THAT THE FUSE IS 150 AMP. | | | PROVIDE RISER DIAGRAM SHOWING EXISTING WIRE AND FUSE | | | SIZE TO HANDLE LOAD STATED IN PANEL SCHEDULE OF | | | APPROXIMATELY 142 AMPS. NEC 215.2, 215.5, 240.4; FBC | | | 17.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|