| Plan Review Notes For Permit 17120962 |
| Permit Number |
17120962 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-04-17 18:34:57 | 04/17/2018 2ND PLUMBING REVIEW**DENIED** | | | | | | 1) ADDRESS MUST BE ON PLAN. FBC 107.2.1 | | | | | | 2) THE WATER HEATER ON YOUR FLORIDA ENERGY EFFICIENCY | | | FORM R405-2014 IS SHOWING THE E.F AS .92. AS OF APRIL | | | 16, 2015 ALL RESIDENTIAL WATER HEATERS ARE REQUIRED TO | | | BE A MIN .95 E.F UP TO 55 GALLONS. THIS IS DEFINED IN | | | THE CODE OF FEDERAL REGULATION (CFR) 75 FR 2012. | | | | | | 3) THE VERTICAL WET VENT THE KITCHEN IS CONNECTED TO | | | ALSO SERVES THE 2ND FLOOR BATHROOM. FBC-R P 3108.4 ONLY | | | ALLOWS VERTICAL VENT VENTING TO BE ON THE SAME FLOOR. | | | PLEASE REVISE YOUR SANITARY ISOMETRIC DRAWING. | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|