| 2017-12-29 13:53:17 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | |
| | 561-805-6718 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1. ON PAGES A0.03 AND A0.18 PLEASE SELECT THE SOUND |
| | PROOFING USED UNDER THE FLOOR SYSTEMS SELECTED. PROVIDE |
| | A MANUFACTURERS TEST REPORT SHOWING COMPLIANCE WITH FBC |
| | 603.1 FLAME SPREAD ? ASTM E-84-09. |
| | |
| | 2. PROVIDE PRODUCT APPROVALS FOR TWO NEW DOORS USED ON |
| | OPENINGS 004 AND 006. |
| | |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR |
| | SUBMITTALS. |
| | |
| | 3. PLEASE CLARIFY ON PAGE A0.03 SYSTEMS NUMBER WL 1001 |
| | AND WL 2003 SHOW THE OPTION OF WOOD FRAMING. |
| | |
| | FBC 603.1 ALLOWABLE MATERIALS IN TYPE I CONSTRUCTION. |
| | |
| | COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS |
| | OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING |
| | APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 |
| | THROUGH 603.1.3: |
| | |
| | 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN: |
| | 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED |
| | FIRE-RESISTANCE RATING IS 2 HOURS OR LESS. |
| | 1.2. NONBEARING EXTERIOR WALLS WHERE FIRE-RESISTANCE |
| | RATED CONSTRUCTION IS NOT REQUIRED. |
| | 1.3. ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES, |
| | FRAMING AND DECKING. |
| | |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 |
| | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |