| Plan Review Notes For Permit 17120924 |
| Permit Number |
17120924 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-17 06:12:00 | 01/17/2018 PLUMBING 1ST REVIEW**DENIED** | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | | | | 1) PLUMBING SANITARY ISOMETRIC DRAWING SHOWS THE WET | | | VENT FOR THE LAV FITTING FACING THE WRONG WAY. FBC-P | | | 706.3 | | | | | | 2) SHOW CLEAR FLOOR SPACES FOR FIXTURES AS REQUIRED. | | | FBC-A 604.3 | | | | | | 3) P-1 SHOW GRAB BARS 33?-36? BUT NOT TO THE TOP OF THE | | | GRIPPING SURFACE AS REQUIRED. FBC-A 609.4 | | | | | | 4) YOUR OVERALL DIMENSION OF THE ROOM (6?) DOES NOT | | | ALLOW FOR THE REQUIRED CLEAR FLOOR SPACE. MIN FINISHED | | | OPENING WOULD BE 7? 1? TO COMPLY WITH FBC-A 604.8 USING | | | MIN REQUIREMENTS FOR FIXTURE SIZES. | | | | | | 5)TOILET PAPER DISPENSERS SHALL BE INSTALLED 7?-9? FROM | | | THE FRONT LIP OF THE TOILET. FBC-A 604.7 | | | | | | 6) YOU MIRROR MOUNTED @ 40? WOULD NOT COMPLY AS IT HAS | | | A STEEL FRAME. PER 603.3 THE MIRROR SHALL BE MOUNTED A | | | MAX 40? ABOVE A LAVATORY TO THE REFLECTIVE SURFACE. | | | | | | TIM HUNT | | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | 561-805-6695 | | | [email protected] | | | |
|