Plan Review Notes
Plan Review Notes For Permit 17120924
Permit Number 17120924
Review Stop P
Sequence Number 1
Notes
Date Text
2018-01-17 06:12:0001/17/2018 PLUMBING 1ST REVIEW**DENIED**
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 1) PLUMBING SANITARY ISOMETRIC DRAWING SHOWS THE WET
 VENT FOR THE LAV FITTING FACING THE WRONG WAY. FBC-P
 706.3
  
 2) SHOW CLEAR FLOOR SPACES FOR FIXTURES AS REQUIRED.
 FBC-A 604.3
  
 3) P-1 SHOW GRAB BARS 33?-36? BUT NOT TO THE TOP OF THE
 GRIPPING SURFACE AS REQUIRED. FBC-A 609.4
  
 4) YOUR OVERALL DIMENSION OF THE ROOM (6?) DOES NOT
 ALLOW FOR THE REQUIRED CLEAR FLOOR SPACE. MIN FINISHED
 OPENING WOULD BE 7? 1? TO COMPLY WITH FBC-A 604.8 USING
 MIN REQUIREMENTS FOR FIXTURE SIZES.
  
 5)TOILET PAPER DISPENSERS SHALL BE INSTALLED 7?-9? FROM
 THE FRONT LIP OF THE TOILET. FBC-A 604.7
  
 6) YOU MIRROR MOUNTED @ 40? WOULD NOT COMPLY AS IT HAS
 A STEEL FRAME. PER 603.3 THE MIRROR SHALL BE MOUNTED A
 MAX 40? ABOVE A LAVATORY TO THE REFLECTIVE SURFACE.
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION