2018-01-03 09:02:251ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120924
 1/3/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE DUCTS PENETRATIONS THROUGH THE FIRE-RATED
 CORRIDOR WALL MAY HAVE TO BE PROTECTED WITH EITHER FIRE
 OR SMOKE DAMPERS HOWEVER ADDITIONAL INFORMATION
 REGARDING THE CORRIDOR WALL NEEDS TO BE ON THE PLAN.
 INDICATE THE HOURLY FIRE-RATING OF THE CORRIDOR WALL ON
 THE PLAN AND CLARIFY IF IT IS A FIRE BARRIER OR A FIRE
 PARTITION. PLEASE REFER TO SECTIONS 607.5.2, 607.5.3,
 AND 607.5.4 AND PROVIDE
  
 THE REQUIRED DAMPERS OR INDICATE HOW THE PENETRATIONS
 ARE MEETING THE EXCEPTIONS LISTED UNDER THE ABOVE
 SECTIONS. PLEASE INDICATE THE TYPE AND SIZE OF THE DUCT
 PENETRATING THE LADIES BATHROOM/CORRIDOR WALL.
  
 2) REFER TO SECTION 607.7 WHICH PROHIBITS FLEX DUCTS
 FROM PASSING THROUGH ANY FIRE-RESISTANCE-RATED
 ASSEMBLY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  