| Notes |
| Date |
Text |
| 2018-01-03 09:02:25 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120924 | | | 1/3/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE DUCTS PENETRATIONS THROUGH THE FIRE-RATED | | | CORRIDOR WALL MAY HAVE TO BE PROTECTED WITH EITHER FIRE | | | OR SMOKE DAMPERS HOWEVER ADDITIONAL INFORMATION | | | REGARDING THE CORRIDOR WALL NEEDS TO BE ON THE PLAN. | | | INDICATE THE HOURLY FIRE-RATING OF THE CORRIDOR WALL ON | | | THE PLAN AND CLARIFY IF IT IS A FIRE BARRIER OR A FIRE | | | PARTITION. PLEASE REFER TO SECTIONS 607.5.2, 607.5.3, | | | AND 607.5.4 AND PROVIDE | | | | | | THE REQUIRED DAMPERS OR INDICATE HOW THE PENETRATIONS | | | ARE MEETING THE EXCEPTIONS LISTED UNDER THE ABOVE | | | SECTIONS. PLEASE INDICATE THE TYPE AND SIZE OF THE DUCT | | | PENETRATING THE LADIES BATHROOM/CORRIDOR WALL. | | | | | | 2) REFER TO SECTION 607.7 WHICH PROHIBITS FLEX DUCTS | | | FROM PASSING THROUGH ANY FIRE-RESISTANCE-RATED | | | ASSEMBLY. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|