| 2018-01-26 09:52:15 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. A.0.1 AND A.0.2 PLEASE REMOVE DETAILS AND |
| | REQUIREMENTS THAT DO NOT APPLY TO THIS PROJECT. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 2. A SEPARATE PERMIT IS REQUIRED FOR THE MAIN BACKFLOW, |
| | GAS AND GREASE INTERCEPTOR IF A NEW ONE IS INSTALLED |
| | PLEASE PLACE NOTE ON THE PLAN. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 3. THE EXISTING GREASE INTERCEPTOR SHALL BE CERTIFIED |
| | BY WPB UTILITIES DEPT CONTACT JEFFERY ODOMS |
| | 561-822-2172 OR [email protected]. PLEASE PLACE NOTE ON |
| | PLAN. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. SHOW ON PLAN, THE MAIN BACKFLOW SHALL BE INSTALLED |
| | NEXT TO THE WATER METER. PER WPB CROSS CONNECTION |
| | MANUAL |
| | |
| | 5. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. MOST OF THESE ARE |
| | POINT OF USE. |
| | PER FBC PL 416.5 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |