| 2018-01-18 11:25:15 | 1ST REVIEW FBC-2014 MECHANICAL, FLORIDA ENERGY |
| | CONSERVATION CODES |
| | PERMIT #17120895 |
| | 1/18/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEMS- SECTION C403.2.1 FBC-14 ENERGY CONSERVATION |
| | AND SECTION 312.1 FBC-14 MECHANICAL. |
| | |
| | 2) PROVIDE ENERGY CALCULATIONS IN COMPLIANCE WITH |
| | SECTION C101.2 FBC-14 ENERGY CONSERVATION. |
| | |
| | 3) SHEET A-1.1: EQUIPMENT 0.32 & 040A ARE SHOWN ON THE |
| | PLAN BUT NOT IN THE SCHEDULE. |
| | |
| | 4) M-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL |
| | GAS-FIRED COOKING APPLIANCES- SECTION 304. |
| | |
| | 5) M-1: THE 1028 SQ. FT. DINING AREA SHOWN IN THE |
| | VENTILATION TABLE DOES NOT MATCH THE 1551 SQ. FT. AREA |
| | SHOWN IN THE TABLE ON LSP-1.0- PLEASE CORRECT. |
| | |
| | 6) M-1: PLEASE EMBOLDEN THE FAINTLY PRINTED NOTES AND |
| | RTU AND O/A LABELS SHOWN ON THE MECHANICAL PLAN- |
| | SECTION 107.2.1.4 WPB AMENDMENTS TO THE FBC. |
| | |
| | 7) M-1: PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF |
| | DAMPERS FOR THE O/A INTAKES- SECTION C403.2.4.4 FBC-14 |
| | ENERGY CONSERVATION. |
| | |
| | 8) M-2: PROVIDE THE WIND DESIGN CRITERIA FOR THE RTU |
| | AND CURB ATTACHMENT DETAILS- SECTION 1609 FBC-14 |
| | BUILDING. |
| | |
| | 9) SHOW THE CONDENSATE PIPING RUNS AND DISCHARGE |
| | LOCATIONS, AND PROVIDE PIPING AND SUPPORT DETAILS- |
| | SECTION 307. |
| | |
| | 10) ADVISORY: SEPARATE PERMITS ARE REQUIRED FOR THE |
| | KITCHEN EXHAUST HOODS, THE FIRE SUPPRESSION SYSTEMS, |
| | AND THE WALK-IN COOLERS AND FREEZER. PLEASE NOTE THAT |
| | COMPLIANCE WITH SECTIONS 508.1.1 (MAKEUP AIR |
| | TEMPERATURE) AND 301.15 WIND RESISTANCE FOR ROOFTOP |
| | FANS WILL BE REQUIRED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |