| 2018-01-23 13:15:36 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ESTIMATED AIC INFORMATION IS NOT ACCEPTABLE. PROVIDE |
| | AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH PANEL |
| | INCLUDING INFORMATION FROM THE POWER COMPANY STATING |
| | WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE |
| | SERVICE TO CONFIRM THE STATED AIC RATING OF THE SERVICE |
| | EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, |
| | 110.10 |
| | 2. BASED ON THE CURRENT AIC CALCULATIONS, PANELS M AND |
| | B DO NOT MEET OR EXCEED THE RATING REQUIRED. WHEN |
| | ACCURATE CALCULATION IS COMPLETED, CONFIRM THAT ALL |
| | PANELS HAVE THE PROPER AIC RATING. NEC 110.9 |
| | 3. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 4. CIRCUIT B-23,25 SHOWS #12 WIRE ON A 25 AMP BREAKER |
| | FOR THE COFFEE MAKER. THE OCP FOR #12 WIRE SHALL NOT |
| | EXCEED THE VALUES IN 240.4(D). PROVIDE CORRECTION. NEC |
| | 240.4(D) |
| | 5. BASED ON THE AREA DESIGNATED FOR "NO ELECTRICAL |
| | CONDUIT IN HOOD AREA" ON SHEET E-2, IT APPEARS THAT |
| | THERE IS ELECTRICAL OUTLETS UNDER THE HOOD THAT WILL |
| | NOT BE SHUT OFF DURING HOOD SHUTDOWN. I SEE A NOTE ON |
| | SHEET E-5 UNDER "HOOD VENTILATION SYSTEM" THAT CALLS |
| | FOR ALL CONTROLLED COOKING EQUIPMENT UNDER HOOD TO BE |
| | SHUT DOWN, BUT THIS SHOULD INCLUDE ALL ELECTRICAL UNDER |
| | HOOD. THIS APPEARS TO INCLUDE CIRCUITS M-2,4,6; B-4; |
| | B-18; B-20; B-37; AND B-41. PROVIDE CLARIFICATION |
| | AND/OR CORRECTIONS AS NEEDED. NFPA 96, SECTION 10.4.1, |
| | FBC 107.2.1 |
| | 6. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| | 107.2.1 |
| | 7. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. SHOW ON PLAN. NEC 250.94 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |