| 2018-01-09 10:49:08 | ****PLAN REVIEW COMMENTS**** |
| | |
| | ART LANGE BUILDING PLANS EXAMINER |
| | |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH, FL 33402 |
| | |
| | 561-805-6718 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | 1. FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING, EXTERIOR WINDOW, AND |
| | DOOR, STOREFRONT SYSTEMS AND A/C ROOF STANDS |
| | SUBMITTALS. |
| | |
| | ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED |
| | SUBMITTAL BY LISTING THEM ON THE COVER SHEET. |
| | |
| | FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| | THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 2. SELECT TYPE OF CONSTRUCTION. IT IS SHOWN AS IIIB |
| | UNSPRINKLERED ON PAGES A.0. ON PAGE LSP 1.0 IT IS SHOWN |
| | AS TYPE IIB UNSPRINKLERED. |
| | FBC 601 TYPES OF CONSTRUCTION |
| | FBC 602.1 GENERAL. |
| | BUILDINGS AND STRUCTURES ERECTED OR TO BE ERECTED, |
| | ALTERED OR EXTENDED IN HEIGHT OR AREA SHALL BE |
| | CLASSIFIED IN ONE OF THE FIVE CONSTRUCTION TYPES |
| | DEFINED IN SECTIONS 602.2 THROUGH 602.5. THE BUILDING |
| | ELEMENTS SHALL HAVE A FIRE-RESISTANCE RATING NOT LESS |
| | THAN THAT SPECIFIED IN TABLE 601 AND EXTERIOR WALLS |
| | SHALL HAVE A FIRE-RESISTANCE RATING NOT LESS THAN THAT |
| | SPECIFIED IN TABLE 602. WHERE REQUIRED TO HAVE A |
| | FIRE-RESISTANCE RATING BY TABLE 601, BUILDING ELEMENTS |
| | SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION |
| | 703.2. THE PROTECTION OF OPENINGS, DUCTS AND AIR |
| | TRANSFER OPENINGS IN BUILDING ELEMENTS SHALL NOT BE |
| | REQUIRED UNLESS REQUIRED BY OTHER PROVISIONS OF THIS |
| | CODE. |
| | |
| | FBC 602.1.1 MINIMUM REQUIREMENTS. |
| | A BUILDING OR PORTION THEREOF SHALL NOT BE REQUIRED TO |
| | CONFORM TO THE DETAILS OF A TYPE OF CONSTRUCTION HIGHER |
| | THAN THAT TYPE WHICH MEETS THE MINIMUM REQUIREMENTS |
| | BASED ON OCCUPANCY EVEN THOUGH CERTAIN FEATURES OF SUCH |
| | A BUILDING ACTUALLY CONFORM TO A HIGHER TYPE OF |
| | CONSTRUCTION. |
| | |
| | 3. ACCESSIBILITY. WOMAN?S RESTROOM DOOR. PROVIDE A |
| | MINIMUM OF 12? ON THE FRONT APPROACH AT THE LATCHED |
| | SIDE OF A DOOR WITH A CLOSURE. SEE PAGES A.1.0 AND |
| | A.1.1. NOTE. DETAIL PROVIDED AT 1/A 6.0 IS AT THE |
| | MINIMUM. |
| | |
| | FBC ACCESSIBILITY 404.2.4.1 DETAIL (C) SWINGING DOORS |
| | AND GATES. |
| | |
| | 4. INTERIOR SPACE DIMENSIONS |
| | |
| | (A)SEE DISTANCE AROUND CART 006. |
| | |
| | (B) DISTANCE BETWEEN BUN RACK 027 AND SINK 060. |
| | |
| | FBC 1208.1 MINIMUM ROOM WIDTHS. |
| | |
| | KITCHENS SHALL HAVE A CLEAR PASSAGEWAY OF NOT LESS THAN |
| | 3 FEET (914 MM) BETWEEN COUNTER FRONTS AND APPLIANCES |
| | OR COUNTER FRONTS AND WALLS. |
| | |
| | 5. PROVIDE A WPS (WELDING PROCEDURE SPEC). HAVE THIS ON |
| | SITE AT TIME OF INSPECTION. |
| | |
| | WELDED OR BOLTED CONNECTIONS |
| | |
| | THE CONTRACTOR IS REQUIRED TO PROVIDE A (WPS) WELD |
| | PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION. |
| | 2014 FBC-B 2204.1 WELDING |
| | 2014 FBC-B 2204.2 BOLTING. |
| | |
| | 6. BUILDING DEMOLITION. |
| | |
| | PROVIDE RELEASES FROM THE FOLLOWING UTILITIES: |
| | |
| | (A) FLORIDA POWER AND LIGHT (FPL) ELECTRIC, FLORIDA |
| | PUBLIC UTILITIES (GAS), WEST PALM BEACH UTILITIES AND |
| | WEST PALM BEACH HISTORIC PRESERVATIONS. |
| | |
| | (B) EXTERMINATION LETTER FROM A LICENSED PEST CONTROL |
| | COMPANY. |
| | |
| | (C) ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S. |
| | THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS? |
| | RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL |
| | ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S. |
| | AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE- |
| | ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION |
| | TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO: |
| | * DEMOLITION OF ALL REGULATED STRUCTURES; |
| | * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES |
| | WHERE ASBESTOS IS DISTURBED OR REMOVED. |
| | NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY. |
| | |
| | FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT |
| | THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING |
| | HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT |
| | (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR |
| | POLLUTION CONTROL SECTION) |
| | |
| | 901 EVERNIA STREET |
| | WEST PALM BEACH, FL 33401 |
| | (561) 355-3070 |
| | |
| | FBC 3303.1 CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS AND A SCHEDULE FOR DEMOLITION |
| | SHALL BE SUBMITTED WHERE REQUIRED BY THE BUILDING |
| | OFFICIAL. WHERE SUCH INFORMATION IS REQUIRED, NO WORK |
| | SHALL BE DONE UNTIL SUCH CONSTRUCTION DOCUMENTS OR |
| | SCHEDULE, OR BOTH, ARE APPROVED. |
| | |
| | FBC 3303.2 PEDESTRIAN PROTECTION. |
| | THE WORK OF DEMOLISHING ANY BUILDING SHALL NOT BE |
| | COMMENCED UNTIL PEDESTRIAN PROTECTION IS IN PLACE AS |
| | REQUIRED BY THIS CHAPTER. |
| | |
| | I HAVE INCLUDED THE DEMOLITION CHECKLIST ALONG WITH |
| | YOUR PERMIT APPLICATION. THIS FORM CAN BE DOWNLOADED ON |
| | OUR WEBSITE AS WELL. |
| | |
| | 7. SEPARATE PERMITS REQUIRED FOR THE FOLLOWING. |
| | |
| | (A) PARKING LOT, LANDSCAPING, SIGNS, HOODS, TEMP |
| | FENCING, TEMP TRAILERS AND AWNINGS. |
| | |
| | (B) TRELLIS WORK WILL BE UNDER A SEPARATE PERMIT. A |
| | NOTE WAS FOUND ON A 1.3. SEE ALSO TRELLIS SHOWN ON SP |
| | 1.3 REFERENCES A DETAIL ON A 1.3 THAT WAS NOT PROVIDED. |
| | |
| | (C) BEFORE SUBMITTING FOR A PARKING LOT PERMIT CHECK ON |
| | WEST PALM BEACH?S PARKING REQUIREMENTS REGARDING SIZES |
| | OF SPACING AND STRIPING DETAILS. MANY OF THE DETAILS |
| | SHOWN ON SP 1.0 ARE NOT COMPLIANT. |
| | |
| | 8. ENERGY EFFICIENCY. |
| | |
| | PROVIDE ENERGY CALCULATIONS AND SHOW COMPLIANCE WITH |
| | FBC 1301.1.1 CRITERIA. |
| | |
| | BUILDINGS SHALL BE DESIGNED AND CONSTRUCTED IN |
| | ACCORDANCE WITH THE FLORIDA BUILDING CODE, ENERGY |
| | CONSERVATION, 103.1.1.1.2 COMMERCIAL AND |
| | MULTIPLE-FAMILY RESIDENTIAL. |
| | COMPLETION OF PROCEDURES DEMONSTRATING COMPLIANCE WITH |
| | THIS CODE FOR COMMERCIAL AND MULTIPLE-FAMILY |
| | RESIDENTIAL BUILDINGS SHALL BE IN ACCORDANCE WITH THE |
| | PROVISIONS OF SECTION 481.229, FLORIDA STATUTES, OR |
| | SECTION 471.003, FLORIDA STATUTES. |
| | |
| | 9. IMPACT FEES |
| | |
| | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT |
| | FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID. |
| | UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE |
| | SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN |
| | IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP |
| | AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE |
| | CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN |
| | BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY |
| | IMPACT FEES AT (561) 233-5025. |
| | |
| | WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2 |
| | 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION. |
| | WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED |
| | SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS |
| | READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE |
| | RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE |
| | FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR |
| | *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN |
| | THE PERMIT PACKAGE. |
| | |
| | A RESPONSE LETTER INDICATING HOW EACH ITEM WAS |
| | ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW. |
| | |