| Plan Review Notes For Permit 17120894 |
| Permit Number |
17120894 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-01-10 11:30:39 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120894 | | | 1/10/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) COMMENT #1 FROM THE 1ST REVIEW WSS NOT ADDRESSED. I | | | HAVE REPRINTED BELOW- PLEASE COMPLY. | | | | | | 1) THE P100 PLAN IS UNACCEPTABLE FOR REVIEW: A) MINIMUM | | | 1/8" SCALE REQUIRED PER SECTION 107.2.1.4 WPB | | | AMENDMENTS TO THE FBC. B) THE ARCHITECT WHO PREPARED | | | THE PLAN SHALL PROVIDE HIS SIGNATURE AND SEAL ON THE | | | PLAN- SECTION 61G15-16.003 FLORIDA ADMINISTRATIVE CODE. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|