| 2017-12-28 12:27:37 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17120894 | | | 12/28/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE P100 PLAN IS UNACCEPTABLE FOR REVIEW: A) MINIMUM | | | 1/8" SCALE REQUIRED PER SECTION 107.2.1.4 WPB | | | AMENDMENTS TO THE FBC. B) THE ARCHITECT WHO PREPARED | | | THE PLAN SHALL PROVIDE HIS SIGNATURE AND SEAL ON THE | | | PLAN- SECTION 61G15-16.003 FLORIDA ADMINISTRATIVE CODE. | | | | | | 2) WIND LOAD ENGINEERING IS REQUIRED FOR INSTALLATION | | | OF THE EXTERIOR CONDENSER PER SECTION 301.15 FBC-14 | | | MECHANICAL, AND SECTION 1609 FBC-14 BUILDING. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|