2019-01-28 09:10:181) WHAT STANDARD ARE THE GAS SIZING TABLES FROM? THERE
 IS NO REFERENCE ON THESE TABLES TO DETERMINE IF THEY
 ARE FROM A STANDARD REFERENCED IN THE 2014 FBC.
 2) REMOVE THE ANCHORING DETAIL FOR THE LP TANK FROM THE
 SUBMITTAL PACKAGE. THIS GAS SYSTEM IS NATURAL GAS. IN
 ADDITION, THE ENGINEER'S SIGNATURE AND SEAL ON THIS
 DOCUMENT CANNOT BE PHOTOCOPIED. IT VIOLATES FL. ADMIN.
 RULE 61G15-23.001. ALSO, THIS ENGINEER'S SEAL HAS BEEN
 NULL AND VOID SINCE 2015.
 3) THE GAS PERMIT APPLICATION STATES "INSTALL TANK AND
 LINE" BUT THE GAS DRAWING SHOWS A NATURAL GAS METER.
 CLARIFY.
 4) THERE ARE TWO DIFFERENT SIZING TABLES FOR THE PE
 PIPE. CLARIFY.
 5) THERE ARE THREE DIFFERENT GAS DRAWINGS THAT HAVE
 BEEN SUBITTED FOR THIS PROJECT. REMOVE THE OLD DRAWINGS
 AND SUBMIT TWO COPIES OF A GAS RISER THAT CLEARLY SHOWS
 THE SCOPE OF WORK TO BE DONE.WPB AMEND TO FBC
 SEC.107.2.1. 6TH REQUEST.
 6) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYSTEM BUT
 YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR A
 LESS THAN 2 PSI SYSTEM. CLARIFY. SUBMIT A COPY OF THE 2
 PSI SIZING TABLE BEING USED OR PLACE A NOTE ON THE
 PLANS REFERENCING THE SIZING TABLE BEING USED. 6TH
 REQUEST.
 4) CLEARLY SHOW THE DISTANCE FROM THE 2 PSI REGULATORS
 TO THE APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES
 402.4 FOR THE PROPER PIPE SIZE AND BTU LOAD. 4TH
 REQUEST.
 5) SHOW THE DISTANCE OF THE GENERATOR FROM THE EXTERIOR
 WALL OF THE STRUCTURE ON THE SURVEY. THE GENERATOR
 SHALL BE LOCATED IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTALLATION MANUAL OR A MINIMUM OF 5 FEET FROM THE
 EXTERIOR WALL OF THE STRUCTURE UNLESS THE WALL IS ONE
 HOUR FIRE RATED PER NFPA 37 SEC. 4.1.4. 4TH REQUEST.
 6) THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE
 SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE.
 THE SIZING TABLE THAT HAS BEEN SUBMITTED DOES NOT SHOW
 THAT IT IS FROM THE 2014 FBC-FUEL GAS CODE. 4TH
 REQUEST.
 7) SUBMIT TWO COPIES OF THE REGULATOR INSTALLATION
 SHEETS. FBC SEC. 107.2.1.4TH REQUEST.
 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR
 SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR 2014 FBC-RES. SEC. G2422.1 .4TH REQUEST.
 9) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
 10) SHOW THE PIPE SIZES FOR ALL THE PIPING INCLUDING
 THE EXISTING. WPB AMEND, TO FBC SEC. 107.2.1.
  
 THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A
 COMPRREHENSIVE REVIEW CANNOT BE DONE.
 NOTE: DO NOT RESUBMIT THESE PLANS UNLESS ALL PLAN
 REVIEW COMMENTS HAVE BEEN ADDRESSED. PLEASE CALL THE
 PLAN REVIEWER TO SET UP AN APPOINTMENT TO GO OVER THESE
 REVIEW COMMENTS.
  
 THE NEXT RESUBMITTAL IS SUBJECT TO 4 TIMES THE PLAN
 REVIEW FEE PER FL. STATUTE 553.80 (2) (B).
  