Plan Review Notes
Plan Review Notes For Permit 17120888
Permit Number 17120888
Review Stop G
Sequence Number 5
Notes
Date Text
2018-11-02 12:56:24NOT ONE OF THE FOLLOWING COMMENTS FROM THE PREVIOUS
 PLAN REVIEW DONE ON 9/14/18 OR 10/1/18 HAVE BEEN
 ADDRESSED.
  
 1) THERE ARE STILL COPIES OF TWO DIFFERENT GAS DRAWINGS
 IN THE SUBMITTAL PACKAGE. REMOVE ALL THE OLD
 PLANS/DOCUMENTS FROM THE SUBMITTAL PACKAGE AND SUBMIT
 TWO COMPLETE SETS OF PLANS FOR REVIEW. FBC 107.1. 4TH
 REQUEST.
 2) YOU HAVE SUBMITTED A GAS PLAN SHOWING AN EXISTING
 DRYER AND WATER HEATER . ACCORDING TO CITY RECORDS
 THERE IS ALSO A GAS STOVE AT 40,000 BTU'S AND THE WATER
 HEATER WAS CHANGED TO A TANKLESS WATER HEATER AT
 140,000 BTU'S WHICH WOULD BRING THE TOTAL BTU LOAD TO
 417,000 BTU'S WITH THE GENERATOR. THE SUBMITTTED GAS
 DRAWING NEEDS TO BE REVISED TO SHOW THE CORRECT BTU
 LOAD. 3RD REQUEST.
 3) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYSTEM BUT
 YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR A
 LESS THAN 2 PSI SYSTEM. CLARIFY. SUBMIT A COPY OF THE 2
 PSI SIZING TABLE BEING USED OR PLACE A NOTE ON THE
 PLANS REFERENCING THE SIZING TABLE BEING USED. 5TH
 REQUEST.
 4) CLEARLY SHOW THE DISTANCE FROM THE 2 PSI REGULATORS
 TO THE APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES
 402.4 FOR THE PROPER PIPE SIZE AND BTU LOAD. 3RD
 REQUEST.
 5) SHOW THE DISTANCE OF THE GENERATOR FROM THE EXTERIOR
 WALL OF THE STRUCTURE ON THE SURVEY. THE GENERATOR
 SHALL BE LOCATED IN ACCORDANCE WITH THE MANUFACTURER'S
 INSTALLATION MANUAL OR A MINIMUM OF 5 FEET FROM THE
 EXTERIOR WALL OF THE STRUCTURE UNLESS THE WALL IS ONE
 HOUR FIRE RATED PER NFPA 37 SEC. 4.1.4. 3RD REQUEST.
 6) THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE
 SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE.
 THE SIZING TABLE THAT HAS BEEN SUBMITTED DOES NOT SHOW
 THAT IT IS FROM THE 2014 FBC-FUEL GAS CODE.3RD REQUEST.
 7) SUBMIT TWO COPIES OF THE REGULATOR INSTALLATION
 SHEETS. FBC SEC. 107.2.1.3RD REQUEST.
 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR
 SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE
 GENERATOR 2014 FBC-RES. SEC. G2422.1 .3RD REQUEST.
  
 THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A
 COMPRREHENSIVE REVIEW CANNOT BE DONE.
 NOTE: DO NOT RESUBMIT THESE PLANS UNLESS ALL PLAN
 REVIEW COMMENTS HAVE BEEN ADDRESSED. PLEASE CALL THE
 PLAN REVIEWER BELOW IF YOU HAVE ANY QUESTIONS.
  
 THE NEXT RESUBMITTAL IS SUBJECT TO 4 TIMES THE PLAN
 REVIEW FEE PER FL. STATUTE 553.80 (2) (B).
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  