| 2018-10-01 16:33:37 | PLAN | | | REVIEW COMMENTS | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SIGNED AND SEALED DRAWINGS THAT WERE SUBMITTED | | | FOR THE AMERICAST GENERATOR PAD DO NOT LIST THE | | | SPECIFIC 12 KW BRIGGS AND STRATTON GENERATOR THAT IS | | | PROPOSED. THERE ARE A COUPLE OF THINGS THAT WILL AFFECT | | | THE SLIDING AND OVERTURN MOMENT OF THE GENERATOR DUE TO | | | THE WIND LOAD. THE WEIGHT OF THIS GENERATOR IS ONLY 318 | | | LBS. WHICH IS LESS THAN THE LIGHTEST MODEL LISTED IN | | | THE TABLE ON THE DRAWINGS. THE LENGTH AND WIDTH | | | DIMENSIONS OF THE GENERATOR ARE SMALLER THAN THE ONES | | | THAT ARE LISTED AND IT IS TALLER. PLEASE SUBMIT | | | ENGINEERING THAT LISTS THE PROPOSED GENERATOR OR THAT | | | HAS THE SAME WEIGHT AND DIMENSIONS. FBC-R301. IF THERE | | | ARE NO PREFAB PADS FOR THIS GENERATOR, THEN YOU CAN | | | FORM AND POUR A CONCRETE PAD AT THE SITE. IF YOU WISH | | | TO DO THIS THEN SUBMIT TWO SETS OF DIMENSIONED PAD | | | DETAILS. SPECIFY THE ANCHOR TYPE, LOCATIONS, NUMBER AND | | | TYPE OF FASTENERS ON THE PLANS. THE ADDRESS OF THE | | | PROJECT, THE PRINTED NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN IS REQUIRED TO BE ON THE | | | DRAWINGS. FBC 107.2.1 | | | | | | | | | | | | | | | | | | |
|