| 2018-09-13 05:58:04 | 1) THERE ARE STILL COPIES OF TWO DIFFERENT GAS DRAWINGS |
| | IN THE SUBMITTAL PACKAGE. REMOVE ALL THE OLD |
| | PLANS/DOCUMENTS FROM THE SUBMITTAL PACKAGE AND SUBMIT |
| | TWO COMPLETE SETS OF PLANS FOR REVIEW. FBC 107.1. 2ND |
| | REQUEST. |
| | 2) YOU HAVE SUBMITTED A GAS PLAN SHOWING AN EXISTING |
| | DRYER AND WATER HEATER . ACCORDING TO CITY RECORDS |
| | THERE IS ALSO A GAS STOVE AT 40,000 BTU'S AND THE WATER |
| | HEATER WAS CHANGED TO A TANKLESS WATER HEATER AT |
| | 140,000 BTU'S WHICH WOULD BRING THE TOTAL BTU LOAD TO |
| | 417,000 BTU'S WITH THE GENERATOR. THE SUBMITTTED GAS |
| | DRAWING NEEDS TO BE REVISED TO SHOW THE CORRECT BTU |
| | LOAD. |
| | 3) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYSTEM BUT |
| | YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR A |
| | LESS THAN 2 PSI SYSTEM. CLARIFY. SUBMIT A COPY OF THE 2 |
| | PSI SIZING TABLE BEING USED OR PLACE A NOTE ON THE |
| | PLANS REFERENCING THE SIZING TABLE BEING USED. 3RD |
| | REQUEST. |
| | 4) CLEARLY SHOW THE DISTANCE FROM THE 2 PSI REGULATORS |
| | TO THE APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES |
| | 402.4 FOR THE PROPER PIPE SIZE AND BTU LOAD. |
| | 5) SHOW THE DISTANCE OF THE GENERATOR FROM THE EXTERIOR |
| | WALL OF THE STRUCTURE ON THE SURVEY. THE GENERATOR |
| | SHALL BE LOCATED A MINIMUM OF 5 FEET FROM THE EXTERIOR |
| | WALL OF THE STRUCTURE UNLESS THE WALL IS ONE HOUR FIRE |
| | RATED PER NFPA 37 SEC. 4.1.4. |
| | 6) THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE |
| | SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE. |
| | THE SIZING TABLE THAT HAS BEEN SUBMITTED DOES NOT SHOW |
| | THAT IT IS FROM THE 2014 FBC-FUEL GAS CODE. |
| | 7) SUBMIT TWO COPIES OF THE REGULATOR INSTALLATION |
| | SHEETS. FBC SEC. 107.2.1. |
| | 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR |
| | SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE |
| | GENERATOR 2017 FBC-RES. SEC. G2422.1 (8). |
| | |
| | THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A |
| | COMPRREHENSIVE REVIEW CANNOT BE DONE. |
| | NOTE: DO NOT RESUBMIT THESE PLANS UNLESS ALL PLAN |
| | REVIEW COMMENTS HAVE BEEN ADDRESSED. PLEASE CALL THE |
| | PLAN REVIEWER BELOW IF YOU HAVE ANY QUESTIONS. |
| | |