2018-09-17 13:26:51PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SIGNED AND SEALED DRAWINGS THAT WERE SUBMITTED
 FOR THE AMERICAST GENERATOR PAD DO NOT LIST THE
 SPECIFIC 12 KW BRIGGS AND STRATTON GENERATOR THAT IS
 PROPOSED. THERE ARE A COUPLE OF THINGS THAT WILL AFFECT
 THE SLIDING AND OVERTURN MOMENT OF THE GENERATOR DUE TO
 THE WIND LOAD. THE WEIGHT OF THIS GENERATOR IS ONLY 318
 LBS. WHICH IS LESS THAN ONE HALF AS MUCH AS THE
 LIGHTEST MODEL LISTED IN THE TABLE ON THE DRAWINGS. THE
 LENGTH AND WIDTH DIMENSIONS OF THE GENERATOR ARE
 SMALLER THAN THE ONES THAT ARE LISTED. PLEASE SUBMIT
 ENGINEERING THAT LISTS THE PROPOSED GENERATOR OR THAT
 HAS THE SAME WEIGHT AND DIMENSIONS. FBC-R301.
  
  
  
  
  
  