| Plan Review Notes For Permit 17120888 |
| Permit Number |
17120888 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-09-17 13:26:51 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE SIGNED AND SEALED DRAWINGS THAT WERE SUBMITTED | | | FOR THE AMERICAST GENERATOR PAD DO NOT LIST THE | | | SPECIFIC 12 KW BRIGGS AND STRATTON GENERATOR THAT IS | | | PROPOSED. THERE ARE A COUPLE OF THINGS THAT WILL AFFECT | | | THE SLIDING AND OVERTURN MOMENT OF THE GENERATOR DUE TO | | | THE WIND LOAD. THE WEIGHT OF THIS GENERATOR IS ONLY 318 | | | LBS. WHICH IS LESS THAN ONE HALF AS MUCH AS THE | | | LIGHTEST MODEL LISTED IN THE TABLE ON THE DRAWINGS. THE | | | LENGTH AND WIDTH DIMENSIONS OF THE GENERATOR ARE | | | SMALLER THAN THE ONES THAT ARE LISTED. PLEASE SUBMIT | | | ENGINEERING THAT LISTS THE PROPOSED GENERATOR OR THAT | | | HAS THE SAME WEIGHT AND DIMENSIONS. FBC-R301. | | | | | | | | | | | | | | | | | | |
|