| Date |
Text |
| 2018-05-30 12:38:31 | THE GAS PLANS ARE LACKING REQUIRED INFORMATION SO A |
| | COMPRREHENSIVE REVIEW CANNOT BE DONE. COMPLY WITH THE |
| | FOLLOWING COMMENTS. |
| | |
| | 1) THE GAS PLANS REFER TO THE 2010 FBC-FUEL GAS. THE |
| | SYSTEM SHALL BE SIZED USING THE 2014 FBC-FUEL GAS CODE. |
| | SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES USED |
| | TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL |
| | GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 |
| | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4, |
| | G2412.8, G2413.1, G2413.2, & G2413.3. THE SUBMITTED |
| | SIZING TABLE DOES NOTE SHOW THAT IT IS FROM THE 2014 |
| | FBC-FUEL GAS. |
| | |
| | 2) THE GAS PLAN NOTES THE SYSTEM AS A 2 PSI SYTEM BUT |
| | YOU HAVE SUBMITTED A SIZING TABLE FOR PE PIPE FOR LESS |
| | THAN A 2 PSI SYSTEM. CLARIFY. |
| | |
| | 4) CLEARLY IDENTIFY THE REGULATORS ON THE GAS DRAWING. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 5) SHOW THE DISTANCE FROM THE 2 PSI REGULATOR TO THE |
| | APPLIANCE. COMPLY WITH 2014 FBC-FUEL GAS TABLES 402.4 |
| | FOR THE PROPER PIPE SIZE AND BTU LOAD. |
| | |
| | 6) SHOW THE TYPE OF UNDERGROUND PIPING AND THE PIPE |
| | SIZE FOR THE GENERATOR. NOTE: GALVANIZED PIPE IS NOT |
| | PERMITTED TO BE INSTALLED UNDERGROUND. |
| | |
| | 7) SHOW THE TYPE OF PIPE AND THE PIPE SIZE AT THE |
| | OUTLET OF THE GAS METER. |
| | |
| | 8) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | FLEXIBLE CONNECTOR TO THE GENERATOR. THE CONNECTOR |
| | SHALL BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE |
| | GENERATOR 2017 FBC-RES. SEC. G2422.1 (8). |
| | |
| | 9) SHOW THE DISTANCE FROM THE GAS METER TO EACH |
| | PRESSURE REGULATOR |
| | |
| | 10) SUBMIT 2 COPIES OF THE MANUFACTURER'S INSTALLATION |
| | MANUAL. WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 11) SHOW THE DISTANCE OF THE GENERATOR FROM THE |
| | EXTERIOR WALL OF THE STRUCTURE ON THE SURVEY. THE |
| | GENERATOR SHALL BE LOCATED A MINIMUM OF 5 FEET FROM THE |
| | EXTERIOR WALL OF THE STRUCTURE UNLESS THE WALL IS ONE |
| | HOUR FIRE RATED PER NFPA 37 SEC. 4.1.4. |
| | |
| | 12) DELETE THE OLD GAS DRAWINGS FROM THE PERMIT PACKAGE |
| | AND SUBMIT TWO COMPLETE SETS OF PLANS FOR REVIEW. WPB |
| | AMEND. TO FBC SEC. 107.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | |
| | |
| | |