| Plan Review Notes For Permit 17120888 |
| Permit Number |
17120888 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-06-19 18:52:01 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ENGINEERING THAT WAS SUBMITTED FOR THE GENERATOR | | | PAD DOES NOT HAVE THE ENGINEER'S ORIGINAL HANDWRITTEN | | | SIGNATURE AS REQUIRED BY FAC 61G-15-23.003. F.S. | | | 471.025 | | | | | | 2) THE PAD ENGINEERING THAT WAS SUBMITTED REFERENCES | | | THE 2010 FBC AND THIS PROJECT IS UNDER THE 2014 FBC. |
|