2017-12-22 11:50:25PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 NOTE: THIS APPLICATION FOR A COMMERCIAL ROOFING REPAIR
 WAS REQUESTED TO BE A TURN AROUND WHILE THE CUSTOMER
 WAITED. THE TWO COMMENTS BELOW WERE VERBALLY PROVIDED
 TO THE CUSTOMER.
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5). . PROVIDE
 TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA NUMBERS
 INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN
 PRESSURES FOR EACH OF THE DIFFERENT ROOFING MATERIALS.
  
 2) FBC EXISTING BUILDING 708.1.1 - NOT MORE THAN 25
 PERCENT OF THE TOTAL ROOF AREA OR ROOF SECTION OF ANY
 EXISTING BUILDING OR STRUCTURE SHALL BE REPAIRED,
 REPLACED OR RECOVERED IN ANY 12-MONTH PERIOD UNLESS THE
 ENTIRE ROOFING SYSTEM OR ROOF SECTION CONFORMS TO
 REQUIREMENTS OF THIS CODE. THE TOTAL AREA OF THE ROOF
 IS 1900 SQFT AND THE APPLICATION IS TO REPAIR 900 SQFT.
 THIS IS MORE THAN 25 PERCENT OF THE ROOF AREA,
 THEREFORE THE ENTIRE ROOF IS REQUIRED TO BE REPLACED.
  
  