| Plan Review Notes For Permit 17120845 |
| Permit Number |
17120845 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-03-07 11:40:36 | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | | 5TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | | SATISFACTORILY HAVE BEEN NOTED AS CORRECTED. ITEMS | | | REMAINING HAVE FURTHER COMMENTS IN PARENTHESES. | | | | | | 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE | | | OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THE | | | ESTIMATE PROVIDED DOES NOT APPEAR TO INCLUDE ALL OF THE | | | WORK. FBC 109.3 (CONTRACT PROVIDED DOES NOT SHOW ALL | | | WORK THAT IS DESCRIBED ON PLANS. PROVIDE ACCURATE COST | | | OF WORK INCLUDING LABOR AND MATERIALS.) | | | 2. CORRECTED. | | | 3. CORRECTED. | | | 4. CORRECTED. | | | 5. CORRECTED. | | | 6. CORRECTED. | | | 7. CORRECTED. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|