| 2018-01-05 13:52:05 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE |
| | OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THE |
| | ESTIMATE PROVIDED DOES NOT APPEAR TO INCLUDE ALL OF THE |
| | WORK. FBC 109.3 |
| | 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR |
| | PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM |
| | BONDING TERMINATION POINT. NEC 215.5, 230, 250.50, |
| | 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC |
| | 107.2.1 |
| | 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3 |
| | 4. PROVIDE CLARIFICATION OF SPACE IN FRONT OF |
| | ELECTRICAL PANEL. IT APPEARS THAT THERE COULD BE A |
| | CABINET THERE, ALTHOUGH THE PLAN DOES NOT STATE EITHER |
| | WAY. THERE MUST BE 3 FEET OF CLEARANCE IN FRONT OF THE |
| | PANEL. NEC 110.26; FBC 107.2.1 |
| | 5. NOTE 3 AND NOTE 9 STATE THAT TAMPER RESISTANT |
| | RECEPTACLES ARE REQUIRED. NOTE 3 QUOTES THE WRONG CODE |
| | SECTION, NEC 406.11, WHICH DOES NOT PERTAIN TO TAMPER |
| | RESISTANT RECEPTACLES. PROVIDE CORRECTION BY REMOVING |
| | REDUNDANT NOTE THAT IS WRONG, OR CORRECTING NOTE. FBC |
| | 107.2.1 |
| | 6. NOTE 7 RELATES TO BROWARD COUNTY. THIS PROJECT IS |
| | NOT LOCATED IN BROWARD, PLEASE REMOVE THIS REFERENCE. |
| | FBC 107.2.1 |
| | 7. PALM BEACH COUNTY PROPERTY APPRAISER WEBSITE STATES |
| | THAT THERE IS NO AC/HEAT IN THIS HOUSE. THERE WAS AN |
| | APPLICATION TO INSTALL 4 A/C'S SUBMITTED TO THE CITY IN |
| | APRIL OF 2017, BUT THIS PERMIT WAS NEVER ISSUED. THE |
| | PLAN SUBMITTED STATES THAT EXISTING UNITS WILL BE |
| | REPLACED, HOWEVER, NONE SHOULD HAVE BEEN INSTALLED |
| | WITHOUT A PERMIT. PLEASE CLARIFY WHAT WILL BE |
| | INSTALLED. PROVIDE DETAIL OF ANY ELECTRICAL INSTALLED |
| | TO THESE UNITS, AS THEY NEED A DEDICATED CIRCUIT. FBC |
| | 107.2.1, NEC 422.12 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |