2018-01-05 13:52:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE
 OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THE
 ESTIMATE PROVIDED DOES NOT APPEAR TO INCLUDE ALL OF THE
 WORK. FBC 109.3
 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR
 PANEL. SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM
 BONDING TERMINATION POINT. NEC 215.5, 230, 250.50,
 250.94, 408.30 FBC RE3706.1, RE3608.1, RE3609.3; FBC
 107.2.1
 3. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE3602.3
 4. PROVIDE CLARIFICATION OF SPACE IN FRONT OF
 ELECTRICAL PANEL. IT APPEARS THAT THERE COULD BE A
 CABINET THERE, ALTHOUGH THE PLAN DOES NOT STATE EITHER
 WAY. THERE MUST BE 3 FEET OF CLEARANCE IN FRONT OF THE
 PANEL. NEC 110.26; FBC 107.2.1
 5. NOTE 3 AND NOTE 9 STATE THAT TAMPER RESISTANT
 RECEPTACLES ARE REQUIRED. NOTE 3 QUOTES THE WRONG CODE
 SECTION, NEC 406.11, WHICH DOES NOT PERTAIN TO TAMPER
 RESISTANT RECEPTACLES. PROVIDE CORRECTION BY REMOVING
 REDUNDANT NOTE THAT IS WRONG, OR CORRECTING NOTE. FBC
 107.2.1
 6. NOTE 7 RELATES TO BROWARD COUNTY. THIS PROJECT IS
 NOT LOCATED IN BROWARD, PLEASE REMOVE THIS REFERENCE.
 FBC 107.2.1
 7. PALM BEACH COUNTY PROPERTY APPRAISER WEBSITE STATES
 THAT THERE IS NO AC/HEAT IN THIS HOUSE. THERE WAS AN
 APPLICATION TO INSTALL 4 A/C'S SUBMITTED TO THE CITY IN
 APRIL OF 2017, BUT THIS PERMIT WAS NEVER ISSUED. THE
 PLAN SUBMITTED STATES THAT EXISTING UNITS WILL BE
 REPLACED, HOWEVER, NONE SHOULD HAVE BEEN INSTALLED
 WITHOUT A PERMIT. PLEASE CLARIFY WHAT WILL BE
 INSTALLED. PROVIDE DETAIL OF ANY ELECTRICAL INSTALLED
 TO THESE UNITS, AS THEY NEED A DEDICATED CIRCUIT. FBC
 107.2.1, NEC 422.12
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  