| Plan Review Notes For Permit 17120840 |
| Permit Number |
17120840 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-02-22 18:18:32 | APPROVED WITH EXCEPTIONS | | | | | | SURFACE DRAINAGE SHALL COMPLY WITH FBC-R401.3. SURFACE | | | DRAINAGE SHALL BE DIVERTED TO A STORM SEWER CONVEYANCE | | | OR OTHER APPROVED POINT OF COLLECTION THAT DOES NOT | | | CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN SURFACE | | | WATER AWAY FROM FOUNDATION WALLS. THE GRADE SHALL FALL | | | A MINIMUM OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET | | | (3048 MM). | | | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER | | | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL | | | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE | | | CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. | | | IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE | | | BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 | | | PERCENT AWAY FROM THE BUILDING. | | | |
|