| Notes |
| Date |
Text |
| 2018-01-17 15:09:24 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED | | | NFPA 70 2011 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NO SMOKE ALARMS ARE SHOWN ON PLANS | | | | | | EXISTING POOL ELECTRIC WOULD NEED TO BE BONDED TO THE | | | DOORS, AND WINDOWS IF WITHIN 5" OF THE POOL. | | | | | | NEW OUTDOOR INSTALLATION CLEARANCES. IN OUTDOOR POOL | | | AREAS, LUMINAIRES, LIGHTING OUTLETS , AND | | | CEILING-SUSPENDED (PADDLE) | | | FANS INSTALLED ABOVE THE POOL OR THE A REA EXTENDING | | | 1.5 M | | | (5 FT) HORIZONTALLY FROM THE INSIDE WALLS OF THE POOL | | | SHALL BE | | | INSTALLED AT A HEIGHT NOT LESS THAN 3.7 M (12 FT) ABOVE | | | THE MAXIMUM | | | WATER LEVEL OF THE POOL. | | | | | | LIGHT FIXTURES NEED TO BE MORE THAN 5' FROM THE POOL | | | WATERS EDGE. | | | | | | |
|