| Date |
Text |
| 2018-04-03 06:34:16 | |
| | 1) YOUR PIPNG ISOMETRIC MUST INCLUDE THE ENTIRE SYSTEM. |
| | THERE IS A DRYER AND RANGE ON THE EXISTING SYSTEM. 2014 |
| | FBC-FUEL GAS SECS. 402.4.1, 402.4.2, OR 2014 FBC-RES. |
| | SEC. G2413. |
| | |
| | 2) LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS |
| | SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 |
| | (37) OR 2014 FBC-RES. SEC. G2413 |
| | |
| | 3) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS |
| | APPLIANCES. THE PLAN NOTES COMBUSTION AIR WILL BE TAKEN |
| | FROM THE GARAGE BUT YOU HAVE SUBMITTED A LETTER FROM |
| | NAVIEN STATING COMBUSTION AIR IS OK TO BE TAKEN FROM |
| | THE ATTIC SPECE. CLARIFY ON THE PLAN WHERE YOU ARE |
| | GETTING THE COMBUSTION AIR AND PROVIDE THE REQUIRED |
| | CCOMBUSTION AIR CALCULATIONS. 2014 FBC- FUEL GAS SECS. |
| | 304.1, 614.5 OR 2014 FBC-RES. SECS.2401.7 AND G2439.4. |
| | |
| | 4) CITY RECORD SHOW EXISTING SYSTEM IS .5LB. INDICATE |
| | THE DELIVERY PRESSURE (PSI) OF THE SYSTEM ON THE PLAN |
| | PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES. SEC. |
| | G2413.2. |
| | |
| | 5) SUBMIT MANUFACTURER'S INSTALLATION MANUAL FOR ALL |
| | NEW GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS |
| | NFPA 54, NFPA 58, AND FBC-2014 FUEL GAS CODE SEC. |
| | 402.2, AND 301.3 OR 2014 FBC-RES. SEC. G2404.3. GAS |
| | APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC |
| | SEC.305.1, FBC-RES. SEC.G2408.1 |
| | |
| | 6) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2014 FBC-FUEL |
| | GAS SECS. 401.4, 401.8 THRU 402.6.1 AND TABLES 402.4 |
| | (1) THRU 402.4 (37) OR 2014 FBC-RES. SEC. G2412.4, |
| | G2412.8, G2413.1, G2413.2, & G2413.3. |
| | |
| | 7) IF 2 PSI SYSTEM SHOW THE LOCATION OF ALL MP |
| | (STEP-DOWN) REGULATORS. A LISTED SHUTOFF VALVE SHALL BE |
| | INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR. |
| | FBC-FUEL GAS SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. |
| | |
| | 8) THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| | |
| | 9) IF 2L PSI SYSTEM SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION. 2014 FGC SEC.410.1. |
| | |
| | 10) THE PLAN SHOWS A 1/2 INCH GAS LINE FOR THE TANKLESS |
| | WATER HEATER BUT THE SPEC SHEETS YOU SUBMITTED SHOW A |
| | MINIMUM 3/4 INCH GAS CONNECTION TO THE UNIT. CLARIFY. |
| | THE GAS SHALL BE SIZED IN ACCORDANCE WITH THE FUEL GAS |
| | CODE OR 2014 FBC-RES. |
| | |
| | 11) SUBMIT A SEPARATE PERMIT APPLICATION FOR THE |
| | INSTALLATION OF THE GAS. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |