| Plan Review Notes For Permit 17120837 |
| Permit Number |
17120837 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-01-19 14:16:25 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. SK-1 SHALL DISCHARGE INTO THE GREASE INTERCEPTOR NOT | | | INTO SANITARY. PER FBC PL 1003.3.1 | | | | | | 2. PROVIDE MANUFACTURE SIZING CALCULATIONS FROM SCHIER | | | FOR GREASE INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 | | | | | | 3. A MIN OF 4" TWO WAY CLEAN OUT IS REQUIRED ON THE | | | OUTLET OF INTERCEPTOR TO BE USED AS A TEST PORT OR A | | | PRE MANUFACTURED TEST PORT CAN BE USED. PER WPB | | | UTILITIES DEPT CONTACT JEFFERY ODOMS WITH ANY QUESTIONS | | | 561-822-2172 | | | | | | 4. A TRAP PRIMER IS REQUIRED ON THE TRENCH DRAIN . PER | | | FBC PL 1002.4 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|