| 2018-01-05 16:43:30 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17120837 |
| | 1/5/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M0.1: THE OUTDOOR DRYBULB AND WETBULB |
| | TEMPERATURES AT 93 AND 80 DEGREES ARE NOT CONSISTENT |
| | WITH ACCA MANUAL N WHICH ARE SET AT 90 AND 78 DEGREES- |
| | PLEASE CORRECT THE PLAN AND THE CALCULATIONS. |
| | |
| | 2) M2.1 EXHAUST VENTILATION AT A RATE OF 0.70 CFMS PER |
| | SQUARE FT. IS REQUIRED FOR THE KITCHEN PER TABLE 403.3. |
| | ALL AIR SUPPLIED TO THE KITCHEN SHALL BE EXHAUSTED AND |
| | CANNOT BE RECIRCULATED PER SECTION 403.2.1(3), AND |
| | TABLE 403.3 FOOTNOTE B. THE CURRENT PLAN IS NOT IN |
| | COMPLIANCE. |
| | |
| | 3) A-5.0: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | COOKING EQUIPMENT: THE INDUCTION COOKTOP, CONVECTION |
| | MICROWAVE, WALL OVEN, AND INDUCTION COOKER. PLEASE NOTE |
| | THAT SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN |
| | EXHAUST HOODS AND FIRE SUPPRESSION SYSTEMS. REFER TO |
| | SECTIONS 506, 507, AND 508 FOR ALL CODE REQUIREMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |