Plan Review Notes
Plan Review Notes For Permit 17120837
Permit Number 17120837
Review Stop M
Sequence Number 1
Notes
Date Text
2018-01-05 16:43:301ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17120837
 1/5/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.1: THE OUTDOOR DRYBULB AND WETBULB
 TEMPERATURES AT 93 AND 80 DEGREES ARE NOT CONSISTENT
 WITH ACCA MANUAL N WHICH ARE SET AT 90 AND 78 DEGREES-
 PLEASE CORRECT THE PLAN AND THE CALCULATIONS.
  
 2) M2.1 EXHAUST VENTILATION AT A RATE OF 0.70 CFMS PER
 SQUARE FT. IS REQUIRED FOR THE KITCHEN PER TABLE 403.3.
 ALL AIR SUPPLIED TO THE KITCHEN SHALL BE EXHAUSTED AND
 CANNOT BE RECIRCULATED PER SECTION 403.2.1(3), AND
 TABLE 403.3 FOOTNOTE B. THE CURRENT PLAN IS NOT IN
 COMPLIANCE.
  
 3) A-5.0: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 COOKING EQUIPMENT: THE INDUCTION COOKTOP, CONVECTION
 MICROWAVE, WALL OVEN, AND INDUCTION COOKER. PLEASE NOTE
 THAT SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN
 EXHAUST HOODS AND FIRE SUPPRESSION SYSTEMS. REFER TO
 SECTIONS 506, 507, AND 508 FOR ALL CODE REQUIREMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  