| 2018-01-08 09:45:20 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| | 107.2.1 |
| | 2. ALL RECEPTACLE OUTLETS IN KITCHEN ARE REQUIRED TO BE |
| | GFCI PROTECTED. PROVIDE CORRECTION. NEC 210.8(B)(2) |
| | 3. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: |
| | 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE |
| | AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL |
| | 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE |
| | OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR |
| | PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, |
| | CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE |
| | 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR |
| | FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC |
| | EC 405.7.1 |
| | 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC 405.5.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |