| 2018-02-12 09:07:23 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE DRAINAGE PLAN THAT WAS SUBMITTED DOES NOT SHOW |
| | HOW THE LOT WILL BE GRADE TO DIVERT THE SURFACE WATER |
| | TO THE APPROVED POINT OF COLLECTION OR STORM DRAIN. |
| | SUBMIT TWO SETS OF A SURFACE DRAINAGE PLAN. FBC-R401.3 |
| | DRAINAGE. SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM |
| | SEWER CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION |
| | THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO |
| | DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE |
| | GRADE SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN |
| | THE FIRST 10 FEET (3048 MM). |
| | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| | CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| | IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| | BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| | PERCENT AWAY FROM THE BUILDING. |
| | FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS |
| | SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE |
| | ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE |
| | AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| | GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS, |
| | FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE |
| | DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE |
| | SURVEY. |
| | |
| | 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR THE THE HORIZONTAL |
| | SLIDING WINDOWS AND THE DOUBLE CASEMENT WINDOWS THAT |
| | ARE SPECIFIED ON THE PLANS. |
| | |
| | 3) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |