2018-06-04 09:14:443RD REVIEW FBC-2017 MECHANICAL
 PERMIT #17120813
 6/4/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE COMPLIANCE DATA LISTED ON THE COMCHECK
 CERTIFICATE NEEDS TO BE UPDATED TO MATCH THE CHANGES TO
 THE AC SYSTEMS.
  
 2) SHEET M202: REFER TO TABLE 305.4 FBC-17 MECHANICAL.
 THE SPACING OF THE PVC CONDENSATE PIPING SUPPORTS SHALL
 BE 4' O.C. PLEASE REVISE NOTE M09 AND SUBMIT A PRODUCT
 DATA SHEET FOR THE SUPPORTS OR LIST AS A DEFFERRED
 SUBMITTAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  