| 2018-04-18 15:57:45 | 2ND REVIEW: FBC 2017 6TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. PLEASE PROVIDE THE DIMENSIONS FOR THE SINGLE USER | | | BATHROOM #437 INCLUDE THE REQUIRED CLEAR FLOOR SPACE | | | FOR THE TOILET AND THE LAVATORY. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | 2. PLEASE PROVIDE THE MANUFACTURE SPECIFICATIONS FOR | | | THE MASTER MIXING VALVE TMV-1 LAWLER 802- MS- ARV PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 3. SHT. P520 DETAIL 5D A VACUUM BREAKER IS REQUIRED ON | | | INLET SIDE OF THE WATER HEATER. PER FBC PL 504.2 | | | | | | 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES | | | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET | | | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 | | | THE MASTER MIXING VALVE DOES NOT COMPLY. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|