Plan Review Notes
Plan Review Notes For Permit 17120813
Permit Number 17120813
Review Stop M
Sequence Number 2
Notes
Date Text
2018-04-20 08:15:252ND REVIEW FBC-2017 MECHANICAL
 PERMIT #17120813
 4/20/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE AC CALCULATIONS INDICATE A COOLING LOAD OF 180
 MBH FOR THE ROOMS AND SPACES SERVED BY RTU-3, HOWEVER
 THE SYSTEM SELECTED HAS A TOTAL COOLING CAPACITY OF
 84.6 MBH- SEE THE RTU-3 SCHEDULE ON M600.
  
 2) AS PREVIOUSLY REQUESTED, AND PER THE REFERENCE NOTE
 IN THE AC SCHEDULES, PLEASE PROVIDE SYMBOLS ON THE
 MECHANICAL PLANS SHOWING THE LOCATIONS OF REQUIRED DUCT
 SMOKE DETECTORS.
  
 3) IT APPEARS FROM THE PLANS AND THE ARCHITECT'S
 RESPONSE NARRATIVE THAT COMPLETE WIND LOAD ENGINEERING
 FOR INSTALLATION OF THE ROOFTOP AC SYSTEMS WILL BE
 DEFERRED. PLEASE NOTE THAT THE ENGINEERING SHALL BE
 SUBMITTED TO THE BUILDING DEPARTMENT FOR REVIEW AND
 APPROVAL PRIOR TO INSTALLATION, AND THE ENGINEERING
 SHALL BE ONSITE AT TIME OF INSPECTION. PLEASE REVIEW
 SECTION 107.3.4.1 WPB AMENDMENTS TO THE FBC-17:
 DEFERRED SUBMITTALS.
  
 4) SHEET M202: INDICATE THE TYPES AND SIZES OF
 CONDENSATE PIPING, AND INDICATE HOW THE PIPING WILL BE
 SUPPORTED AND ANCHORED TO THE ROOF SURFACE. PLEASE
 PROVIDE A DETAIL THAT SHOWS THE PIPE SUPPORTS AND
 REQUIRED SPACING OF THE SUPPORTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  