| 2018-04-17 15:36:22 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2.CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | (RESPONSE LETTER STATED THIS NOTE WAS ADDED TO SHEET |
| | E-201, BUT THE NOTE WAS NOT THERE.) |
| | 8. CORRECTED. |
| | 9. CORRECTED. |
| | 10. SPECIFY WIRE SIZES FOR ALL COMPONENTS OF THE |
| | GROUNDING ELECTRODE SYSTEM. NEC 250.50, 250.66; FBC |
| | 107.2.1 (GROUNDING ELECTRODE CONDUCTORS ARE REQUIRED TO |
| | BE SIZED FOR THE SEPARATELY DERIVED SYSTEM PER NEC |
| | 250.30. THE # 4 WIRE SPECIFIED ON PLAN IS NOT CODE |
| | COMPLIANT. PROVIDE CORRECTION.) |
| | 11. CORRECTED. |
| | 12. CORRECTED. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |