Plan Review Notes
Plan Review Notes For Permit 17120813
Permit Number 17120813
Review Stop B
Sequence Number 2
Notes
Date Text
2018-04-16 14:51:032014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17120813
 ADD: 301 NORTHPOINT PKWY.
 CONT: TBD/ PRO COMMERCIAL LLC
 TEL: 515-597-4700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY, APRIL 16/ 2018
 ACTION: DENIED
  
 NOTICE ONLY NO ACTION NEED TO BE TAKEN AT THIS TIME.
 ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 APPLICABLE BUILDING CODE: THE RESPONSE LETTER STATES
 THAT THE AHCA REVIEW REQUIRES YOUR PLANS BE DESIGNED TO
 THE 2017 FBC, PROBABLY BECAUSE OF THE SUBMITTAL DATE.
 THE BUILDING PLANS WERE SUBMITTED IN DECEMBER OF 2017
 BEFORE THE 31 OF THE MONTH. THAT WAS THE DATE THE 2017
 FLORIDA BUILDING CODE WAS ADOPTED, OUR REVIEWS HAVE TO
 BE UNDER THE 2014 FBC. PLEASE NOTE UNDER THE LIFE
 SAFETY SHEET 02-G010 YOU MAY ELECT TO SHOW THE
 REQUIREMENTS FOR BOTH CODES AND LISTING BOTH CODES.
  
 PLEASE NOTE AHCA REVIEWING UNDER THE 2017 EDITION OF
 THEIR CODE WILL HAVE COMMENTS NOT FOUND UNDER THE 2014
 FBC. THE ENTIRE SECTION OF FBC-B 450 NURSING HOMES HAS
 BEEN REVISED TO UPDATE THE NURSING HOME TO THE NATIONAL
 RECOGNIZED STANDARD FOR NURSING HOME DESIGN SIMILAR TO
 HOW THE HOSPITAL OR AMBULATORY SURGICAL CENTER
 REQUIREMENTS ARE WRITTEN. BECAUSE THE GUIDELINES ARE
 UPDATED EVERY FOUR YEARS THE NURSING HOMES IN FLORIDA
 WILL KEEP UP WITH THE LATEST CHANGES AND TECHNOLOGIES
 OF A NATIONAL ADOPTED AND RECOGNIZED CODE.
  
 1) COMPLIED. BUILDING NOT IN FLOOD ZONE.
  
 2) COMPLIED. ACCESSIBLE PARKING WITH CITY STANDARD
 94-485.
  
 3-5) COMPLIED.
 6) 2ND REQUEST. SEMI- COMPLIED WITH COMBUSTIBLE
 MATERIALS IN TYPE I / II BUILDINGS, . PLEASE NOTE SHEET
 33-A501 SEE DETAILS C2 & C5. DETAIL C2 SHOWS ? INCH AND
 WOOD BLOCKING NOT FIRE RETARDANT TREATED. DETAIL F6
 SHOWS THE USE OF ? INCH MARINE GRADE PLYWOOD
 SUB-STRATE. PLEASE SHOW COMPLIANCE WITH 2014 FBC-B:
 603.1.1 1.FIRE-RETARDANT-TREATED WOOD SHALL BE
 PERMITTED IN:
 1.1.NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
 1.2.NONBEARING EXTERIOR WALLS WHERE
 FIRE-RESISTANCE-RATED CONSTRUCTION IS NOT REQUIRED.
 1.3.ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING.
  
 7) SEE COMMENT FOR APPLICABLE CODES BEFORE PLAN REVIEW
 #1 COMMENT.
  
 8) SEMI-COMPLIED. THE RESPONSE COMMENT INDICATES THE
 SLEEPING ROOMS ARE UNDER SECTION 450 FOR NURSING HOMES.
 THE HEADING OF 450.3.2.5 THE CLEAR OPENING OF THE
 RESIDENT ROOM WINDOW WIDTH AND HEIGHT SHALL HAVE A
 MINIMUM OF 20 FEET (6.10 M) UNOBSTRUCTED VISTA TO ANY
 PERMANENT STRUCTURE, OR EQUIPMENT, AND 15 FEET (4.57 M)
 UNOBSTRUCTED VISTA TO ANY VEHICULAR PARKING AREAS OR
 PROPERTY LINE MEASURED HORIZONTALLY FROM THE PLANE OF
 THE WINDOW. I DO NOT SEE ANY WINDOW SCHEDULE ON THE
 ARCHITECTURAL SHEETS SHOWING COMPLIANCE.
  
 9) BUILDING PROVISO/ DEFERRED SUBMITTALS: 2014 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS ,
 VENTILATORS
 (G) PRE-ENGINEERED A/C STANDS
  
 9A) PROVISO: IDENTIFY GLAZING/ MULLIONS. PLEASE
 IDENTIFY ON THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 DESIGNER OF RECORD AND BEFORE SUBMISSION TO THE
 BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF
 GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 9B) PROVISO: W. P. B. 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 9C) PROVISO: NEW COMMENT. EFIS SYSTEMS: PLEASE PROVIDE
 THE PRODUCT APPROVAL FOR THE SYSTEM TO BE INSTALLED.
 PLEASE ALSO PROVIDE THE MANUFACTURERS INSTALLATION
 BROCHURE PROVIDING COMPLIANCE WITH 2014 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 9D) NEW COMMENT. SHEET S000 INDICATES THE WIND DESIGN
 CRITERIA AS VULT AND EXPOSURE B. PLEASE NOTE IN
 REVIEWING UNDER THE 2014 FBC-B1609.4.2 SURFACE
 ROUGHNESS. THE C SURFACE ROUGHNESS CAN BE AS LITTLE AS
 ANY SURFACE ROUGHNESS SHALL ALSO APPLY TO ANY BUILDING
 LOCATED WITHIN SURFACE ROUGHNESS B-TYPE TERRAIN WHERE
 THE BUILDING IS WITHIN 100 FEET (30 M) HORIZONTALLY IN
 ANY DIRECTION OF OPEN AREAS OF SURFACE ROUGHNESS C OR
 D-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) IN THE UPWIND DIRECTION AND A WIDTH GREATER THAN 150
 FEET (46 M). WITH THE C TYPE EXPOSURE THERE WILL BE
 MULTIPLIERS FOR THE MEAN ROOF HEIGHT OF THE BUILDING.
 SEE 2014 FBC-B TABLE 1609.7(2). ADJUSTMENT FACTOR FOR
 BUILDING HEIGHT AND EXPOSURE, (?). PLEASE EXPRESS
 PRESSURES ALSO IN VASD SINCE THE PRODUCT APPROVALS ARE
 IN VASD.
  
 9E) NEW COMMENT. THE STRUCTURAL CALCULATIONS SUBMITTED
 WILL NEED TO BE RECALCULATED UNDER THE 180 VULT AND
 EXPOSURE C. PLEASE ALSO NOTE FLORIDA ADMINISTRATIVE
 CODE 61G15-23.002(2)(B) FL. ADMIN. CODE. A COVER SHEET
 WITH LISTED PAGES OR INDEX SHEET FOR ENGINEERING
 SPECIFICATIONS MAY BE USED AND THAT SHEET MUST BE
 SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION &
 PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX LISTING HOW MANY PAGES ARE COVERED UNDER
 THE COVER SHEET OR INDEX SHEET.
  
 10-11) PLEASE NOTE THE PLANS SUBMITTED SHOW ON SHEET
 13-S001 STATEMENT OF SPECIAL INSPECTIONS. PLEASE BE
 AWARE THE REQUIREMENTS UNDER THE 2012 IBC 1704 SECTIONS
 4 & 5 THESE ARE INSPECTIONS REQUIRED FOR MASONRY AND
 UNIQUE WORK NOT SPECIFICALLY ADDRESS IN THE CODE. IN
 THE 2014 & 2017 CODE THESE SECTIONS ARE RESERVED. UNDER
 FLORIDA STATUTE 553.71(7) THRESHOLD BUILDINGS REQUIRES
 A THRESHOLD INSPECTOR (SPECIAL INSPECTOR). / FL S. S.
 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 UNDER THE 1ST REVIEW OUR BUILDING PLANS REVIEWER SAW
 THE WORDING STATEMENT FOR SPECIAL INSPECTIONS AND TOOK
 IT THAT YOU WISH TO HAVE A THRESHOLD INSPECTOR ONSITE
 FOR THE DURATION OF THE PROJECT AT THE OWNERS OWN COST.
 THE CITY HAS A RESIDENT INSPECTOR PROGRAM FOR SMALLER
 SITES WHICH DO NOT MEET THE STATE THRESHOLD REQUIREMENT
 AND THAT IS A RESIDENT INSPECTOR, THIS CAN QUALIFY AS A
 CONSTRUCTION TYPE II-B BUILDING BUT IT USUALLY STARTS
 AT 20,000 SQ. FT. THIS BUILDING (ADDITION IS ONLY
 11,000 SQ. FT. AND FOR THE MASONRY PORTION THE CITY
 BUILDING INSPECTORS CAN DO THE INSPECTIONS. SINCE THERE
 IS BOLTED AND WELDED STEEL CONNECTIONS TO SIMPLIFY THE
 REQUIREMENTS FOR A RESIDENT INSPECTOR AND ADDITIONAL
 EXPENSE TO THE OWNER WE HAVE REQUESTED THE FOLLOWING
 REQUIREMENTS:
 WELDED OR BOLTED CONNECTIONS
 THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
 FOR ADDITIONAL INFORMATION ON THIS SUBJECT PLEASE
 CONTACT EITHER:
 SAMANTHA HILL CHIEF PLANS EXAMINER 561-805-6724
 OR
 RICHARD GATHRIGHT ASSISTANT B. O. 561-805-6679
  
 11A) NEW COMMENT. PLEASE REVIEW SHEET 02-G010 THE LIFE
 SAFETY PLAN. THE VERSION 2 NOW HAS A NEW MAINTENANCE
 ROOM 104A. NOTE ON THE PLANS STATE TEMPORARY EGRESS
 FROM THE EXISTING BUILDING TO BE THROUGH THE NEW
 MAINTENANCE 104. THIS SPACE IS TO BE CONSTRUCTED,
 EXCEPT FOR MILLWORK PRIOR TO CLOSING THE EXISTING WEST
 EXIT. PLEASE REVIEW UNDER THE 2014 FBC-B 1014.2 EGRESS
 THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION. PLEASE SEE EXCEPTION # 4, EGRESS SHALL
 NOT PASS THROUGH KITCHENS, STORAGE ROOMS, CLOSETS OR
 SPACES USED FOR SIMILAR PURPOSES.
  
 11B) NEW COMMENT. THE LIFE SAFETY SHEET 02-G010
 INDICATES BETWEEN THE EXISTING BUILDING AND NEW
 ADDITION A WALL MARKED AS SB-1 A SMOKE BARRIER (1 HOUR
 RATING)/ USE: SMOKE COMPARTMENT WALL WITH DOOR. THE
 FLOOR PLAN ON SHEET 023-A101 INDICATES DOOR 100A IN THE
 DOOR SCHEDULE (34-A600) AS A 20 MINUTE FIRE RATING AND
 DOOR 118 IN THE SAME SMOKE COMPARTMENT WALL WITH NO
 FIRE RATING. PLEASE REVIEW FBC-B
 TABLE 716.5 SMOKE BARRIERS ? HOUR PROTECTION. FBC-B
 709.3 FIRE-RESISTANCE RATING. A 1-HOUR FIRE-RESISTANCE
 RATING IS REQUIRED FOR SMOKE BARRIERS.
  
 11C) NEW COMMENT. THE LIFE SAFETY SHEET 02-G010
 INDICATES A 2ND SMOKE BARRIER / SMOKE COMPARTMENT WALL
 AND DOOR # 400. IN THE DOOR SCHEDULE DOOR # 400 DOES
 NOT INDICATE A FIRE RATING. PLEASE REVIEW FBC-B
 TABLE 716.5 SMOKE BARRIERS ? HOUR PROTECTION. FBC-B
 709.3 FIRE-RESISTANCE RATING. A 1-HOUR FIRE-RESISTANCE
 RATING IS REQUIRED FOR SMOKE BARRIERS.
  
 11D) NEW COMMENT. PLEASE NOTE ON SHEET 24-A102 THE MAIN
 ROOF IS DEPICTED AS A FLAT ROOF WITH 1/4 INCH SLOPE PER
 FOOT. THE PLAN SHOWS WHAT APPEARS TO BE ROOF DRAINS
 WITH OVERFLOW SCUPPERS. IT APPEARS WE HAVE NO ROOF
 DRAINS BUT OD OVERFLOW DRAINS, SEE DETAIL D6 PLEASE
 CLARIFY. THE OTHER ISSUE IS WHAT WOULD APPEAR TO BE
 OVERFLOW SCUPPERS, THEY ARE LEVEL WITH THE LOWES POINT
 IN THE ROOF, MAKING THEM THROUGH THE WALL SCUPPERS WITH
 A CONDUCTOR HEAD ON THE EXTERIOR OF THE WALL. THE
 THROUGH THE WALL SCUPPERS DO NOT STATE THEY ARE FOR
 EMERGENCY USE, IF THEY ARE TO BE USED AS THE OVERFLOW
 SCUPPERS THEY WILL NEED TO COMPLY WITH:
 FBC-B 1503.4.1 SECONDARY (EMERGENCY OVERFLOW) DRAINS OR
 SCUPPERS. WHERE ROOF DRAINS ARE REQUIRED, SECONDARY
 (EMERGENCY OVERFLOW) ROOF DRAINS OR SCUPPERS SHALL BE
 PROVIDED WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS
 ABOVE THE ROOF IN SUCH A MANNER THAT WATER WILL BE
 ENTRAPPED IF THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY
 REASON. THE INSTALLATION AND SIZING OF SECONDARY
 EMERGENCY OVERFLOW DRAINS, LEADERS AND CONDUCTORS SHALL
 COMPLY WITH SECTIONS 1106 AND 1107, AS APPLICABLE, OF
 CHAPTER 11 OF THE FLORIDA BUILDING CODE, PLUMBING.
  
 1503.4.2.1 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  