| Date |
Text |
| 2018-02-12 09:12:16 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHOW THE CLEAR FLOOR SPACE FOR THE TOILETS AND |
| | LAVATORY WITH DIMENSIONS. PER FBC ACC 604.3.1, 606.2 |
| | |
| | 2. SHOW COMPLIANCE WITH FBC ACC 610.3 IN TRANSFER-TYPE |
| | SHOWERS, THE SEAT SHALL EXTEND FROM THE BACK WALL TO A |
| | POINT WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. |
| | THE TOP OF THE SEAT SHALL BE 17 INCHES (430 MM) MINIMUM |
| | AND 19 INCHES (485 MM) MAXIMUM ABOVE THE BATHROOM |
| | FINISH FLOOR. SEATS SHALL COMPLY WITH 610.3.1 OR |
| | 610.3.2. PER FBC ACC 608.4 |
| | |
| | 3. PLEASE SHOW COMPLIANCE WITH FBC ACC |
| | 604.5.1 SIDE WALL. |
| | THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM) |
| | LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM |
| | THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM |
| | FROM THE REAR W 604.5.2 REAR WALL. |
| | THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| | INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| | 609.4 POSITION OF GRAB BARS. |
| | GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| | 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| | MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| | THE GRIPPING SURFACE |
| | 608.3.1 TRANSFER TYPE SHOWER COMPARTMENTS. |
| | IN TRANSFER TYPE COMPARTMENTS, GRAB BARS SHALL BE |
| | PROVIDED ACROSS THE CONTROL WALL AND BACK WALL TO A |
| | POINT 18 INCHES (455 MM) FROM THE CONTROL WALL. |
| | |
| | 4. ALL BATHROOMS IN PATIENT ROOMS SHALL COMPLY WITH FBC |
| | ACC 805.2 PER FBC ACC 223.2.2 |
| | |
| | 5. SHOW COMPLIANCE WITH FBC ACC 608.5.1 TRANSFER TYPE |
| | SHOWER COMPARTMENTS. |
| | IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS, |
| | FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON |
| | THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM) |
| | MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE |
| | SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL |
| | 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE |
| | SEAT TOWARD THE SHOWER OPENING. |
| | |
| | 6. PLEASE PROVIDE A PLUMBING FIXTURE COUNT BREAK DOWN |
| | COMPLYING WITH FBC PL 403.2 SEPARATE FACILITIES. WHERE |
| | PLUMBING FIXTURES ARE REQUIRED, SEPARATE FACILITIES |
| | SHALL BE PROVIDED FOR EACH SEX. |
| | |
| | 7. PROVIDE DIMENSIONS ON THE SCUPPER. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 8. JUST FOR CLARIFICATION THE SCUPPER IS THE MAIN ROOF |
| | DRAIN AND THE ROUND ROOF DRAIN LOCATED OUT ON THE ROOF |
| | DECK IS THE OVERFLOW DRAIN. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 9. THE DISCHARGE FROM THE OVERFLOW DRAIN SHALL COMPLY |
| | WITH FBC PL 1108.2 SEPARATE SYSTEMS REQUIRED. |
| | SECONDARY ROOF DRAIN SYSTEMS SHALL HAVE THE END POINT |
| | OF DISCHARGE SEPARATE FROM THE PRIMARY SYSTEM. |
| | DISCHARGE SHALL BE ABOVE GRADE, IN A LOCATION THAT |
| | WOULD NORMALLY BE OBSERVED BY THE BUILDING OCCUPANTS OR |
| | MAINTENANCE PERSONNEL. |
| | |
| | 10. SHT. P701 SHOW THE TRAPS ON THE FLOOR DRAINS, |
| | LAVATORY, FLOOR SINKS AND SHOWERS. PER WPB AMEND TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | 11. SHT. P701 DETAIL 3A AND ON THE END OF THE BUILDING |
| | DRAIN A HORIZONTAL DRY VENT IS SHOWN WITCH IS NOT |
| | ALLOWED ALL VENT S SHALL CONNECT ABOVE THE CENTERLINE |
| | OF THE HORIZONTAL DRAIN AND RISE VERTICALLY TO A POINT |
| | ABOVE THE FLOOD LEVEL RIM OF THE HIGHEST FIXTURE IT IS |
| | SERVING. PER FBC PL 905.3 AND 905.4 |
| | |
| | 12. SHT. P701 THE OVER FLOW ROOF DRAINS APPEAR TO |
| | CONNECT TO THE SANITARY SYSTEM PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 13. SHT. P702 PLEASE SHOW ON THE WATER ISOMETRIC, |
| | VALVES ON ALL DROPS, AIR HAMMER ARRESTORS. PER FBC PL |
| | 604.9, 606.1(5) |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |