| 2018-01-26 17:17:14 | 1ST REVIEW FBC-2014 MECHANICAL , ENERGY CONSERVATION |
| | CODES , ASHRAE 170-2008, GUIDELINES FOR DESIGN AND |
| | CONSTRUCTION OF HEALTH CARE FACILITIES- 2010. |
| | PERMIT #17120057 |
| | 1/26/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | |
| | 1) IN ACCORDANCE WITH SECTION C403.2.1 FBC-14 PROVIDE |
| | COOLING AND HEATING CALCULATIONS FOR THE RTU'S, AND THE |
| | PTAC UNITS. |
| | |
| | 2) THE ARCHITECT AND ENGINEER OF RECORD SHALL PROVIDE |
| | ELECTRONIC SIGNATURES AND SEALS ON THE COMCHECK |
| | COMPLIANCE CERTIFICATE- SECTION 61G15-23.005 FAC. |
| | |
| | 3) SHEETS G010 & M201: THERE ARE MISSING FIRE DAMPERS |
| | WHERE DUCTS ARE PENETRATING THE FIRE-RATED WALLS AT |
| | STORAGE 401, SOILED UTILITY 431, & LINEN STORAGE 433. |
| | |
| | 4) M201: REFER TO SECTION 607.5.4 AND PROVIDE SMOKE |
| | DAMPERS FOR ALL DUCTS PENETRATING THE CORRIDOR WALLS, |
| | UNLESS THE WALL IS NOT REQUIRED TO HAVE SMOKE AND DRAFT |
| | CONTROL DOORS, OR IF MEETING ONE OF THE THREE |
| | EXCEPTIONS LISTED UNDER THE CODE SECTION. |
| | |
| | 5) M201: PROVIDE A SYMBOL ON THE PLAN TO INDICATE THE |
| | LOCATIONS OF REQUIRED DUCT SMOKE DETECTORS PER SECTION |
| | 606.2.1. INDICATE HOW THE DEVICES WILL BE SUPERVISED, |
| | AND THE SEQUENCE OF OPERATION RELATING TO SHUTDOWN OF |
| | THE SYSTEM(S) WHEN A DETECTOR ACTUATES- SECTIONS 606.4 |
| | AND 606.4.1;. |
| | |
| | 6) PROVIDE THE WIND LOAD DESIGN CRITERIA AND COMPLETE |
| | ENGINEERED DETAILS FOR INSTALLATION OF THE RTU'S AND |
| | CURBS- SEE SECTION 301.15 FBC-14 MECHANICAL, AND |
| | SECTION 1609 FBC-14 BUILDING. |
| | |
| | 7) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE RTU'S AND |
| | THE PTAC UNITS- SECTION 307. |
| | |
| | 8) PROVIDE DUCT INSTALLATION DETAILS: TYPE OF DUCTWORK, |
| | PRESSURE CLASSIFICATION, INSULATION THICKNESS AND |
| | R-VALUE, AND SUPPORT, HANGING, AND CONNECTION DETAILS. |
| | |
| | 9) VERIFY THAT THE PTAC UNITS ARE FOR RECIRCULATION |
| | ONLY AND WILL NOT PROVIDE OUTSIDE AIR AS NOTED IN |
| | SECTION 4.1-8.2.1(2) GUIDELINES FOR DESIGN AND |
| | CONSTRUCTION OF HEALTH CARE FACILITIES. OTHERWISE |
| | MINIMUM MERV 7 FILTERS ARE REQUIRED PER TABLE 6-1 |
| | ASHRAE 170-2008. |
| | |
| | 10) REFER TO SECTION 6.3.1 ASHRAE 170-2008 AND VERIFY |
| | HEIGHT CLEARANCE REQUIREMENTS FOR O/A INTAKES ON THE |
| | ROOF OR AT GRADE. |
| | |
| | 11) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS |
| | WATER HEATER. |
| | |
| | 12) SHOW HOW ACCESS WILL BE PROVIDED TO THE ROOF FOR |
| | SERVICE AND REPLACEMENT OF THE ROOF TOP MECHANICAL |
| | EQUIPMENT- SECTION 306.5. |
| | |
| | 13) PLEASE SEE BUILDING REVIEW COMMENTS RELAIVE TO |
| | FLOOD ELEVATION AND VERIFY ALL MECHANICAL EQUIPMENT |
| | WILL BE LOCATED AT OR ABOVE THE REQUIRED FLOOD |
| | ELEVATION HEIGHT- SECTION 301.16. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |