2018-04-18 16:54:511ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE THE SIZING TABLE FROM THE FBC FUEL
 GAS 2014 5TH EDITION THAT WAS USED IN SIZING SYSTEM.
 PER WPB AMEND TO FBC 107.2.1
  
 2. LABEL TYPE OF PIPE BEING USED. PER WPB AMEND TO FBC
 107.2.1
  
 3. PLEASE LIST PRESSURE IN PSI FOR SERVICE PRESSURE AND
 PRESSURE DROP IN OF WC. PER WPB AMEND TO FBC 107.2.1
  
 4. THE TOTAL DEVELOPED LENGTH FROM WATER HEATER SHALL
 BE MEASURED ALL THE WAY TO METER.PER WPB AMEND TO FBC
 107.2.1
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  