| 2018-02-01 14:30:07 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, |
| | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| | SYSTEMS, SIGNS, SITE LIGHTING, AND SWIMMING POOLS |
| | (WHERE APPLICABLE) ARE NOT INCLUDED IN THE SCOPE OF |
| | THIS PLAN REVIEW. PROVIDE A BLOCK NOTE INDICATING THE |
| | REQUIRED SEPARATE PERMITS AND DATA SPECIFICATION SHEET |
| | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. FBC 105.1, |
| | 107.2.1 |
| | 2. WHY DOES THE 400 KW GENERATOR, WHICH HAS A CAPACITY |
| | OF APPROXIMATELY 1111 AMPS, SHOW A 1600 AMP BREAKER? |
| | WHAT WILL BE THE LOAD ON THIS GENERATOR? PROVIDE LOAD |
| | CALCULATION. NEC 220, 215.2 |
| | 3. PROVIDE LOAD CALCULATION FOR MAIN SERVICE AND EACH |
| | PANEL, INCLUDING EXISTING AND NEW LOADS. SOME PANEL |
| | SCHEDULES CURRENTLY SHOW NO LOAD. PROVIDE CORRECTION. |
| | NEC 220, 215.2, 215.5; FBC 107.2.1 |
| | 4. PANEL EME1 IS SHOWN AS BEING FED WITH 4 SETS OF 500 |
| | KCMIL WIRE, WHICH WOULD HAVE AN AMPACITY OF 1520 AMPS, |
| | ON A 300 AMP BREAKER TO A 300 AMP PANEL. CLARIFY AND/OR |
| | CORRECT. FBC 107.2.1; NEC 215.2, 408.30 |
| | 5. A DISCREPANCY EXIST BETWEEN THE RISER DIAGRAM AND |
| | THE PANEL SCHEDULE FOR PANEL EMDP. THE RISER DIAGRAM |
| | SHOWS THIS AS A 1600 AMP PANEL. THE PANEL SCHEDULE |
| | SHOWS THIS AS A 600 AMP PANEL. CLARIFY AND CORRECT. FBC |
| | 107.2.1 |
| | 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 7. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| | SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| | AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| | 8. FEED FROM NEW LSI TO PANEL MDP1A IS SHOWN AS 5 SETS |
| | OF 500 KCMIL WIRE, WHICH HAS AN AMPACITY OF 1900 AMPS, |
| | ON A 600 AMP BREAKER TO A 600 AMP PANEL. CLARIFY AND/OR |
| | CORRECT. FBC 107.2.1; NEC 215.2, 408.30 |
| | 9. SHOW COMPLIANCE WITH PANELBOARD BONDING AS REQUIRED. |
| | NEC 517.14 |
| | 10. SPECIFY WIRE SIZES FOR ALL COMPONENTS OF THE |
| | GROUNDING ELECTRODE SYSTEM. NEC 250.50, 250.66; FBC |
| | 107.2.1 |
| | 11. PROVIDE DETAIL LAYOUT OF MAIN ELECTRICAL ROOM, |
| | SHOWING ALL REQUIRED CLEARANCES AND MEANS OF EGRESS. |
| | NEC 110.26; FBC 107.2.1 |
| | 12. PROVIDE DETAIL OF LABELING FOR MAINS. NEC 230.2(E) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |