| Notes |
| Date |
Text |
| 2018-04-06 11:05:57 | 2ND REVIEW FBC-2017 MECHANICAL | | | PERMIT #17120809 | | | 4/6/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M6.02: THE CALCULATED OCCUPANT LOAD USED TO | | | DETERMINE THE VENTILATION FOR THE FITNESS ROOMS IS NOT | | | IN COMPLIANCE WITH TABLE 403.3 WHICH REQUIRES 40 | | | OCCUPANTS PER 1000 S.F. PLEASE CORRECT. | | | | | | 2) M1.11: AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS- | | | EITHER MOTORIZED OR GRAVITY- SHALL BE PROVIDED FOR THE | | | O/A DUCTS- SECTION C403.2.4.4 FBC-14 ENERGY | | | CONSERVATION. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|