| 2018-04-07 13:38:23 | 2ND REVIEW: FBC 2014 5TH EDITION |
| | |
| | GAS COMMENTS: |
| | |
| | 1. THE PLAN NOTES #S 1,2,3 ON THE GAS RISER DO NOT |
| | MATCH UP TO THE PLAN NOTES THEMSELVES PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF |
| | THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, |
| | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY |
| | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK |
| | PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | 3. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE |
| | OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF THE |
| | TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS |
| | BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED |
| | PER NFPA 58 SECTION 3-2.2.7(H). |
| | |
| | 4. SECOND STAGE REGULATORS ARE REQUIRED AT THE |
| | APPLIANCE TO REDUCE PRESSURE FROM 2PSI DOWN TO 11.0 IN |
| | WC PLEASE SHOW ON RISER AND PROVIDE MANUFACTURE |
| | SPECIFICATIONS FOR ALL REGULATORS. PER FBC FG 410.1 AND |
| | 410.2 |
| | |
| | 5. IF LP TANK IS UNDER SEPARATE PERMIT PLEASE INDICATE |
| | ON PLAN. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |