Plan Review Notes
Plan Review Notes For Permit 17120809
Permit Number 17120809
Review Stop G
Sequence Number 2
Notes
Date Text
2018-04-07 13:38:232ND REVIEW: FBC 2014 5TH EDITION
  
 GAS COMMENTS:
  
 1. THE PLAN NOTES #S 1,2,3 ON THE GAS RISER DO NOT
 MATCH UP TO THE PLAN NOTES THEMSELVES PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 2. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 3. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE
 OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF THE
 TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  
 4. SECOND STAGE REGULATORS ARE REQUIRED AT THE
 APPLIANCE TO REDUCE PRESSURE FROM 2PSI DOWN TO 11.0 IN
 WC PLEASE SHOW ON RISER AND PROVIDE MANUFACTURE
 SPECIFICATIONS FOR ALL REGULATORS. PER FBC FG 410.1 AND
 410.2
  
 5. IF LP TANK IS UNDER SEPARATE PERMIT PLEASE INDICATE
 ON PLAN. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  