| 2018-01-31 15:13:05 | 1ST REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | 1. SHT. A0.02 INDEX OF PLUMBING DRAWINGS IT LIST |
| | E1.11P, ED1.11P THESE ARE ELECTRIC SHEETS PLEASE |
| | CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT. A0.02 INDEX OF PLUMBING DRAWINGS P1.11 IS |
| | LISTED BUT MISSING FROM PLAN SET, P0.10, P6.02 ARE IN |
| | THE PLAN SET BUT NOT LISTED SHEETS PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. SHT. A1.21 AND A1.22 LIST C13 FIRE PLACE IN NOTES |
| | BUT COULD NOT LOCATE ON PLAN SHEETS PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. SHT. A4.21 DETAIL #1 IN BATHROOMS 13, 14 IT SHOWS |
| | 17?- 19? TO THE CENTERLINE OF THE TOILET THOSE |
| | DIMENSIONS ONLY APPLY TO AMBULATORY STALL THIS IS A |
| | WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT AND SHALL BE |
| | 16?- 18?.PER FBC ACC 604.2 |
| | |
| | 5. SHT. P6.01 HOT WATER MIXING VALVE WATTS USG-B IS NOT |
| | LISTED AS LEAD FREE YOU CAN USE THE LFUSG-B IT IS |
| | LISTED AS LEAD FREE BY MANUFACTURE SPEC. PER FBC PL |
| | 605.2.1 |
| | |
| | 6. SHT P6.02 VALVES REQUIRED AT ALL WATER PIPING DROPS. |
| | PER FBC PL 606.1 (5) |
| | |
| | 7. SHT. P6.02 SHOW AIR HAMMER ARRESTOR VALVES AND TRAP |
| | PRIMERS ON ISOMETRIC DRAWINGS. PER FBC PL 604.9, 1002.4 |
| | |
| | 8. SHT. P6.02 LABEL AND SIZE UNMARKED PIPE ON WATER |
| | ISOMETRIC. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. PROVIDE PLUMBING FLOOR PLAN. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 10. PLEASE CLARIFY IS THE JANITOR SINK NEW OR EXISTING. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 11. SHT. P0.10 PROVIDE ISOMETRIC DRAWINGS FOR FLOOR |
| | DRAINS. WPB AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | 12. SHT. P0.10 IF THE FLOOR DRAINS ARE CONNECTED TO |
| | SANITARY THEY SHALL BE PROTECTED FROM DISCHARGE OF |
| | STORM WATER. PER WPB CODE OF ORDINANCES SEC. 90-126(5) |
| | |
| | 13. SHT. P0.10 POOL DISCHARGE CANNOT GO TO SANITARY. |
| | PER WPB CODE OF ORDINANCES SEC. 90-126(5) |
| | |
| | 14. PLACE NOTE ON PLAN A SEPARATE PERMIT IS REQUIRED |
| | FOR BACKFLOWS AND FOUNTAIN. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |