Plan Review Notes
Plan Review Notes For Permit 17120809
Permit Number 17120809
Review Stop M
Sequence Number 1
Notes
Date Text
2018-01-25 16:04:041ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17120809
 1/25/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER OF RECORD SHALL PROVIDE ELECTONIC
 SIGNATURES AND SEALS ON THE MECHANICAL PLANS AND THE
 ENERGY COMPLINCE FORM C402-2014 IN COMPLIANCE WITH
 SECTION 61G15-23.005 FAC.
  
 2) SHEET D1.12: SHOW THE LOCATIONS OF KEY NOTE D ON THE
 PLAN.
  
 3) M1.11: PLEASE LABEL THE OUTSIDE AIR DUCTS ON THE
 PLAN, AND PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF
 DAMPERS IN ACCORDANCE WITH SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  