| Notes |
| Date |
Text |
| 2018-01-25 16:04:04 | 1ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION | | | CODES | | | PERMIT #17120809 | | | 1/25/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENGINEER OF RECORD SHALL PROVIDE ELECTONIC | | | SIGNATURES AND SEALS ON THE MECHANICAL PLANS AND THE | | | ENERGY COMPLINCE FORM C402-2014 IN COMPLIANCE WITH | | | SECTION 61G15-23.005 FAC. | | | | | | 2) SHEET D1.12: SHOW THE LOCATIONS OF KEY NOTE D ON THE | | | PLAN. | | | | | | 3) M1.11: PLEASE LABEL THE OUTSIDE AIR DUCTS ON THE | | | PLAN, AND PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF | | | DAMPERS IN ACCORDANCE WITH SECTION C403.2.4.4 FBC-14 | | | ENERGY CONSERVATION. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|