Plan Review Notes
Plan Review Notes For Permit 17120809
Permit Number 17120809
Review Stop B
Sequence Number 1
Notes
Date Text
2018-01-19 13:17:14****PLAN REVIEW COMMENTS****
  
 ART LANGE BUILDING PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33402
  
 561-805-6718 [email protected]
  
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION W/2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION / FRC FLORIDA RESIDENTIAL CODE
 2017 6TH EDITION
  
 1. OK
  
 2. INCLUDE PRESSURES ON THE WINDOW AND DOOR SCHEDULES
 ON PAGES A 7.01 AND A 7.02.
 FBC 107.3.5.1.1(8) - PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-CHAPTER 16.
  
 3. ON PAGE A 4.30 #4 A BAR TOP IS SHOWN AT 42 INCHES.
 IS AN ADA COMPLIANT BAR TOP PROVIDED AS WELL.
  
 4. WELDED OR BOLTED CONNECTIONS
  
 THE CONTRACTOR IS REQUIRED TO PROVIDE A (WPS) WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION.
 2014 FBC-B 2204.1 WELDING
 2014 FBC-B 2204.2 BOLTING.
  
 5. PRODUCT APPROVALS
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
 ALTERNATIVELY YOU CAN SUBMIT THESE LATER AS A DEFERRED
 SUBMITTAL BY LISTING THEM ON THE COVER SHEET.
 INCLUDE THE OVERHEAD DOOR ON THIS LIST.
  
 FBC 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  
 WHEN RESUBMITTING, PLEASE COMPLETE A RESUBMITTAL FORM:
  
 HTTP://WPB.ORG/DEVELOPMENT/WPCONTENT/UPLOADS/SITES/33/2
 013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 THIS FORM IS ALSO AVAILABLE AT THE BUILDING DIVISION.
 WHEN RESUBMITTING, SWAP OUT SHEETS WHICH HAVE CHANGED
 SO THAT THERE ARE TWO COMPLETE, COLLATED SETS OF PLANS
 READY FOR PERMIT ISSUANCE. OLD SHEETS ARE TO BE
 RETAINED IN THE PERMIT APPLICATION PACKAGE (SEPARATE
 FROM THE PERMIT SETS) AND MARKED *OLD SHEETS* OR
 *VOID*. PLEASE KEEP BOTH SETS OF OLD VOIDED SHEETS IN
 THE PERMIT PACKAGE.
  
 A RESPONSE LETTER INDICATING HOW EACH ITEM WAS
 ADDRESSED WILL HELP TO EXPEDITE PLAN REVIEW.
  