| 2018-02-28 17:38:17 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE LOCATION OF THE JOB IS INCORRECTLY IDENTIFIED AS |
| | 807 - 5TH STREET ON THE COVERSHEET, CS-1 AND IN THE |
| | TITLE BLOCKS OF THE OTHER SHEETS. PLEASE CORRECT. FBC |
| | 107.2.1 |
| | |
| | 2) THE DIGITAL FOLDER LABELED SOIL REPORT IS EMPTY. |
| | PLEASE CLARIFY. FBC 107.2.1 |
| | |
| | 3) THE PRODUCT APPROVAL NUMBER THAT IS LISTED ON SHEET |
| | A-3.0 FOR THE LOMANCO ROOF VENTS DOES NOT MATCH THE |
| | PRODUCT APPROVALS THAT WERE SUBMITTED (NOA |
| | NO.16-0510.28). FS 553.842 |
| | |
| | 4) THE TRUSS LAYOUT PLAN AND THE TRUSS DRAWINGS |
| | REFERENCE THE DESIGN CODE AS THE 2017 FBC. THE PERMIT |
| | WAS APPLIED FOR ON DECEMBER 20, 2017 AND THE 2014 FBC |
| | IS THE CODE THAT APPLIES TO THIS PROJECT. THE PLANS |
| | SPECIFY THE 2014 FBC. PLEASE REVISE TRUSS DOCUMENTS |
| | ACCORDINGLY. FS CHAPTER 553 |
| | |
| | 5) THE PERMIT VALUATION HAS BEEN INCREASED FROM |
| | $137,200.00 TO $162,135.00 BASED ON THE CURRENT ICC |
| | VALUATION DATA. FBC 109.3 |
| | |
| | 6) THE ENERGY CALCULATIONS ARE ON THE 2017 FBC FORMS |
| | AND THE EQUIPMENT SIZING CALCULATIONS ARE BASED ON THE |
| | 2017 FBC. THE 2014 FBC- RESIDENTIAL APPLIES TO THIS |
| | PROJECT, THE 2017 FBC APPLIES TO PREMITS THAT ARE |
| | APPLIED FOR AFTER JANUARY 1, 2018. FS CHAPTER 553 |