2017-12-20 13:19:14RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- FLAT ROOF RAS 117 CALCULATIONS SUBMITTED:
 A) THE DESIGN PARAMETERS SPECIFIED BY THE ENGINEER ON
 THE COVER PAGE ARE FOR A WIND SPEED OF 170 MPH BUT
 CALCULATIONS SUBMITTED ON THE SECOND PAGE ARE BASED ON
 160 MPH. REVISE THE CALCULATIONS THE AS REQUIRED.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 B) IT LOOKS LIKE CALCULATIONS SUBMITTED ARE COLOR
 COPIES OF THE ENGINEER'S SEAL AND SIGNATURE. ENGINEER
 TO PROVIDE CALCULATIONS WITH ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 471 FLORIDA STATUES
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  