Plan Review Notes
Plan Review Notes For Permit 17120629
Permit Number 17120629
Review Stop P
Sequence Number 1
Notes
Date Text
2017-12-21 10:44:221) SUBMIT A SANITARY RISER AND WATER RISER DIAGRAM FOR
 REVIEW FOR THE ADDED SHOWER AND FOR THE ADDED WASHING
 MACHINE.WPB AMEND. TO FBC SEC. 107.3.5.1.3.
 2) SUBMIT MANUF. SPECIFICATIONS FOR THE NEW SHOWER
 VALVE. THE SHOWER VALVE SHALL CCOMPLY WITH 2014 FBCR
 SEC.P2708.3.
 3) SUBMIT INFORMATION AS TO THE TYPE OF SHOWER RECEPTOR
 THAT WAS INSTALLED. COMPLY WITH 2014 FBCR SEC.P2709.
 4) SHOWER WALLS SHALL BE FINISHED IN ACCORDANCE WITH
 2014 FBCR-SECS.P2710.1, R307.2.
 5) SUBMIT MANUF. SPECIFICATIONS FOR THE NEW WATER
 HEATER. WATER HEATERS SHALL BE INSTALLED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE
 INSTALLATION MANUAL SHALL BE ON THE JOBSITE FOR
 INSPECTION. 2014 FBCR SEC.M2005.1.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW